START-UP

LOCATION BAROMETRIC RELIEF OR POWER EXHAUST “SIDE #2”

23.28”

TYP

“END #2”

“END #1”

42.62

TYP

ALTERNATE LOCATION (END)

ECONOMIZER

HOOD

“SIDE #1”

23.28”Fig. 56 — Wiring Field-Supplied Unloaders for 42.62”

R/AS/A

42.56”

ECONOMIZER

HOOD

42” MIN.

12.94

R/A(UNIT

OPENING)

S/A

J BOX

PLENUM RATED CABLE

(FIELD SUPPLIED)

J BOX

NOTE: 024-048, 020-050 SIZES SHOWN (2 POWER EXHAUST FANS) 060, 054-068 SIZES HAVE 3 POWER EXHAUST FANS. ALL UNIT SIZES HAVE THE SAME SIZE POWER EXHAUST.

Fig. 55 — Power Exhaust Relocated to Side Return Duct

BASE MODULE

START-UP

Use the following information and Start-Up Checklist on pages CL-1 and CL-2 to check out unit PRIOR to start-up.

DISCRETE OUTPUTS

COMP #2 UNLOADER COM COMP #1 UNLOADER

CYCLIC COND FAN COM CONT COND FAN

POWER EXHAUST

COM POWER EXHAUST

ELEC HEAT 2

COM

ELEC HEAT 1

T39

T38

T37

T36

T35

T34

T31

T32

T33

T30

T29

T28

UL2

UL1

Unit Preparation — Check that unit has been installed in accordance with these installation instructions and applicable codes.

Compressor Mounting — Loosen the compressor hold-down bolts until sidewise movement of the washer under each holddown bolt head can be obtained. Do not loosen com- pletely as bolts are self-locking and will maintain adjustment.

Service Valves — Ensure that the suction, discharge, and liquid line service valves are open. Damage to the compressor could result if they are left closed.

ECONOMIZER

4-20 mA OUPUT

T26

Internal Wiring — Check all electrical connections in unit control boxes; tighten as required.

Fig. 56 — Wiring Field-Supplied Unloaders for

Constant Volume Units

Refrigerant Service Ports — Each refrigerant system has one suction port located in the top of the compressor motor casing. All units also have one service port on the liquid line valve and one on the compressor discharge valve. Be sure that caps on the ports are tight.

58

Page 58
Image 58
Carrier 48AW, 48EW, 48EY024-068, 48AY020-060, 48EK, 48AK Start-Up, Wiring Field-SuppliedUnloaders for, Constant Volume Units