Carrier 48AJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48EJ specifications 236.3/230.9

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 38
Image 38
236.3/230.9

Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont)

UNIT SIZE

NOMINAL

VOLTAGE RANGE

COMPRESSOR

 

OFM

 

IFM

POWER

POWER

No. 1

No. 2

 

 

EXHAUST

SUPPLY

48AJ,AK,

VOLTAGE

 

 

 

 

 

 

 

AW,AY

(3 PH, 60 Hz)

Min

Max

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

FLA

MCA

MOCP*

 

 

(total)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

59.4/54.0

236.3/230.9

300/300

 

 

 

 

 

 

 

 

 

 

 

23.6/23.6

259.9/254.5

300/300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

69.2

345

69.2

345

4

 

5.3

25

74.8/68.0

253.1/244.9

300/300

 

 

(ea)

23.6/23.6

276.7/268.5

350/300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

88/80.0

269.6/259.6

350/300

 

 

 

 

 

 

 

 

 

 

 

23.6/23.6

293.2/283.2

350/350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

27

102.6

125

 

 

 

 

 

 

 

 

 

 

 

12.6

115.2

125

 

 

 

 

 

 

 

 

 

 

 

 

 

050

460

414

508

28.8

173

28.8

173

4

 

2.7

25

34

110.9

125

 

(ea)

12.6

123.5

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

40

118.4

150

 

 

 

 

 

 

 

 

 

 

 

12.6

131.0

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

22

91.7

110

 

 

 

 

 

 

 

 

 

 

 

12.6

104.3

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

26.7

120

26.7

120

4

 

2.4

25

27

96.8

110

 

 

(ea)

12.6

109.4

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

32

103.0

125

 

 

 

 

 

 

 

 

 

 

 

12.6

115.6

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

74.8/68.0

291.3/284.5

350/350

 

 

 

 

 

 

 

 

 

 

 

35.4/35.4

326.7/319.9

400/400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

82.1

446

82.1

446

6

 

5.3

30

88/80.0

306.0/296.5

350/350

 

 

(ea)

35.4/35.4

341.4/331.9

400/400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

114/104

338.5/326.0

450/400

 

 

 

 

 

 

 

 

 

 

 

35.4/35.4

373.9/361.4

450/450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

34

148.3

175

 

 

 

 

 

 

 

 

 

 

 

18.9

167.2

200

 

 

 

 

 

 

 

 

 

 

 

 

 

060

460

414

508

43.6

223

43.6

223

6

 

2.7

30

40

154.3

175

 

(ea)

18.9

173.2

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

52

168.4

200

 

 

 

 

 

 

 

 

 

 

 

18.9

187.3

225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

27

119.3

150

 

 

 

 

 

 

 

 

 

 

 

18.9

138.2

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

34.6

164

34.6

164

6

 

2.4

30

32

124.3

150

 

 

(ea)

18.9

143.2

175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

41

134.9

175

 

 

 

 

 

 

 

 

 

 

 

18.9

153.8

175

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

*Fuse or HACR circuit breaker per NEC.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

38

Page 38