Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AJ, 48EJ specifications 30.8/28.0

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 37
Image 37
Manual background

Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont)

UNIT SIZE

NOMINAL

VOLTAGE RANGE

COMPRESSOR

OFM

 

IFM

POWER

POWER

No. 1

No. 2

 

EXHAUST

SUPPLY

48AJ,AK,

VOLTAGE

 

 

 

 

 

 

AW,AY

(3 PH, 60 Hz)

Min

Max

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

FLA

MCA

MOCP*

 

 

(total)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

30.8/28.0

180.5/177.7

225/225

 

 

 

 

 

 

 

 

 

 

23.6/23.6

204.1/201.3

250/250

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

57.1

266

57.1

266

4

5.3

15

46.2/42.0

195.9/191.7

250/225

 

(ea)

23.6/23.6

219.5/215.3

250/250

 

 

 

 

 

 

 

 

 

 

20

59.4/54.0

209.7/203.7

250/250

 

 

 

 

 

 

 

 

 

 

23.6/23.6

233.3/227.3

250/250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

14

82.4

100

 

 

 

 

 

 

 

 

 

 

12.6

95.0

110

 

 

 

 

 

 

 

 

 

 

 

 

035

460

414

508

25.6

120

25.6

120

4

2.7

15

21

89.4

110

(ea)

12.6

102.0

125

 

 

 

 

 

 

 

 

 

 

20

27

95.8

110

 

 

 

 

 

 

 

 

 

 

12.6

108.4

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

11

66.7

80

 

 

 

 

 

 

 

 

 

 

12.6

79.3

90

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

20.5

96

20.5

96

4

2.4

15

17

72.7

90

 

(ea)

12.6

85.3

100

 

 

 

 

 

 

 

 

 

 

20

22

78.1

100

 

 

 

 

 

 

 

 

 

 

12.6

90.7

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

46.2/42.0

211.0/206.8

250/250

 

 

 

 

 

 

 

 

 

 

23.6/23.6

234.6/230.4

300/250

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

57.1

266

69.2

345

4

5.3

20

59.4/54.0

224.2/218.8

250/250

 

(ea)

23.6/23.6

247.8/242.4

300/300

 

 

 

 

 

 

 

 

 

 

25

74.8/68.0

241.0/232.8

300/300

 

 

 

 

 

 

 

 

 

 

23.6/23.6

264.6/256.4

300/300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

21

93.4

110

 

 

 

 

 

 

 

 

 

 

12.6

106.0

125

 

 

 

 

 

 

 

 

 

 

 

 

040

460

414

508

25.6

120

28.8

173

4

2.7

20

27

99.4

125

(ea)

12.6

112.0

125

 

 

 

 

 

 

 

 

 

 

25

34

107.7

125

 

 

 

 

 

 

 

 

 

 

12.6

120.3

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

17

80.5

100

 

 

 

 

 

 

 

 

 

 

12.6

93.1

110

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

20.5

96

26.7

120

4

2.4

20

22

85.5

110

 

(ea)

12.6

98.1

110

 

 

 

 

 

 

 

 

 

 

25

27

90.6

110

 

 

 

 

 

 

 

 

 

 

12.6

103.2

125

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

*Fuse or HACR circuit breaker per NEC.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x 457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.