Table 35 — User Defined Set Points

SET POINT

FORMAT

DESCRIPTION

LIMITS

DEFAULT

NAME

 

 

 

 

OHSP

xx.xF

Occupied Heat Set Point

55 to 80 F

68 F

OCSP

xx.xF

Occupied Cool Set Point

55 to 80 F

78 F

UHSP

xx.xF

Unoccupied Heat Set Point

35 to 80 F

55 F

UCSP

xx.xF

Unoccupied Cool Set Point

75 to 110 F

90 F

SASP

xx.xF

Supply Air Set Point

45 to 70 F

55 F

OATL

xx.xF

Hi OAT Lockout Temperature

55 to 75 F

65 F

NTLO

xx.xF

Unoccupied OAT Lockout Temperature

40 to 70 F

50 F

RTIO

xx.x

Reset Ratio

0 to 10

3

LIMT

xx.xF

Reset Limit

0 to 20° F

10° F

MDP

xxx%

Minimum Damper Position

0 to 100%

20%

LOWMDP

xxx%

Low Temperature Minimum

0 to 100%

100%

Damper Position Override

 

 

 

 

IAQS

xxxx

IAQ Set Point

1 to 5000 PPM

650 PPM

UHDB

xx.xF

Unoccupied Heating Deadband

0 to 10° F

1° F

UCDB

xx.xF

Unoccupied Cooling Deadband

0 to 10° F

1° F

LTMP

xxx%

Low Temp. Min. Position

0 to 100%

10%

HTMP

xxx%

High Temp. Min. Position

0 to 100%

35%

PES1

xxx%

CV Power Exhaust Stage 1 Point

0 to 100%

25%

PES2

xxx%

CV Power Exhaust Stage 2 Point

0 to 100%

75%

LEGEND

 

 

 

 

CV — Constant Volume

 

 

 

IAQ — Indoor Air Quality

 

 

 

OAT — Outdoor-Air Temperature

 

 

 

Table 36 — Software Control Link Points

SET POINT

DESCRIPTION

SET POINT

DESCRIPTION

 

 

 

CV Data

SPT

Space Temperature

HS2

Heat Stage 2

SAT

Supply-Air Temperature

STO

Space Temp. Offset

RAT

Return-Air Temperature

CVPE1

CV Power Exhaust Stg 1

OAT

Outside-Air Temperature

CVPE2

CV Power Exhaust Stg 2

CLSP

Control Set Point

 

VAV Data

CCAP

Cooling % Total Capacity

HIR

Heat Interlock Relay

HCAP

Heating % Total Capacity

SPTRESET

Space Temp. Reset

ECOS

Economizer Active

CMP1

Compressor 1

SFSTAT

Supply Fan Status

CMP1SAFE

Compressor 1 Safety

SF

Fan Relay

CMP2

Compressor 2

ECONPOS

Economizer Position

CMP2SAFE

Compressor 2 Safety

IQMP

Min. Damper Position

ULD1

Unloader 1

PEXE

Power Exhaust Enable

ULD2

Unloader 2

FLTS

Filter Status

OFC1

Outdoor Fan 1

FAS

Field Applied Status

OFC2

Outdoor Fan 2

RMTOCC

Remote Occupied Mode

Y1

Y1 — Call for Cool 1

 

General Data

Y2

Y2 — Call for Cool 2

HS1

Heat Stage 1

W1

W1 — Call for Heat 1

ENTH

Enthalpy

W2

W2 — Call for Heat 2

IAQI

Indoor Air Quality

G

G — Call for Fan

IAQO

Outdoor Air Quality

CDEVCODE

CONQUEST DEVICE CODE

SATRES

SAT Reset

CDEVURST

CONQUEST UNIT RESET

ALMLIGHT

Alarm Warning Light

CDEVBCAK

CONQUEST BROADCAST ACK

DL

Demand Limit Switch

PE1

Mod. Power Exhaust Stg 1

EVAC

Evacuation

PE2

Mod. Power Exhaust Stg 2

PRES

Pressurization

PE3

Mod. Power Exhaust Stg 3

PURG

Smoke Purge

PE4

Mod. Power Exhaust Stg 4

FSD

Fire Shutdown

PE5

Mod. Power Exhaust Stg 5

 

 

PE6

Mod. Power Exhaust Stg 6

LEGEND

 

 

 

CV — Constant Volume

VAV — Variable Air Volume

81

Page 81
Image 81
Carrier 48EY024-068, 48EW, 48AW, 48AY020-060, 48EK, 48AK, 48AJ, 48EJ User Defined Set Points, Software Control Link Points

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.