Passive Components for RS-485 Networks

Technical Specifications

The following table shows the technical specifications of the various bus connectors:

Table 4-4 Technical Specifications of the IP 20-compliant Bus Connectors

Order numbers:

6ES7 972-

... 0BA50-0XA0

... 0BB50-0XA0

6GK1 500-

0FC00

PG socket

0BA50: no

no

 

0BB50: yes

 

 

 

 

Max. transmission rate

9.6 Kbps to 12 Mbps

9.6 Kbps to 12 Mbps

 

 

 

Cable outlet

90 °

180 °

 

 

 

Terminating resistor

Integrated terminating resistor

Integrated terminating resistor

 

can be activated with sliding

can be activated with sliding

 

switch.

switch.

 

Disconnect function:

Disconnect function:

 

When the resistor is activated,

When the resistor is activated,

 

the outgoing bus is

the outgoing bus is disconnected.

 

disconnected. Attachment with

Attachment with insulation

 

insulation displacement system

displacement system for

 

for FastConnect system

FastConnect system

 

 

 

Interfaces

 

 

– to PROFIBUS node

9-pin sub-D connector

9-pin sub-D connector

– to PROFIBUS LAN cable

4 insulation displacement

4 insulation displacement

 

terminals for all FastConnect

terminals for all FastConnect

 

PROFIBUS cables (except for

PROFIBUS cables (except for FC

 

FC process cable)

process cable)

 

 

 

Power supply

4.75 to 5.25 V DC

4.75 to 5.25 V DC

(must be supplied by the DTE)

 

 

 

 

 

Current consumption

max. 5 mA

max. 5 mA

 

 

 

Permitted ambient conditions

 

 

– Operating temperature

0 ° C to +60 ° C

0 ° C to +60 ° C

– Transport/storage temperature

–25 ° C to +80 ° C

–25 ° C to +80 ° C

– Relative humidity

max. 75% at +25 ° C

max. 75% at +25 ° C

 

 

 

Construction

 

 

– Dimensions (W x H x D)

72.7x16x34

61.7x16x35

– Weight

approx. 50 g

approx. 50 g

 

 

 

Degree of protection

IP20

IP20

 

 

 

Connectable PROFIBUS cable

8 " 0.5 mm

8 " 0.5 mm

diameter

 

 

 

 

 

PROFIBUS Networks SIMATIC NET

4-27