Siemens SIMATIC NET PROFIBUS manual Cable Lengths for Plastic and PCF FO Paths, Fiber-optic cable

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 83
Image 83

Configuring Networks

3.2.3Cable Lengths for Plastic and PCF FO Paths

The length of the transmission path on fiber-optic cables is not dependent on the transmission rate.

Each node on the optical PROFIBUS network has repeater functionality so that the following distance information relates to the distance between two adjacent, interconnected PROFIBUS nodes.

The maximum cable length between two PROFIBUS nodes depends on the type of fiber-optic cable used and the optical network components.

Table 3-7

Permitted Cable Lengths with Integrated Optical Interfaces or OBT

 

 

 

Fiber-optic cable

Maximum cable

For 1 Network (= 32

SIMATIC NET

lengths between two

nodes) (in m)

 

PROFIBUS

nodes (in m)

 

 

 

 

Plastic fiber-optic,

50

1550

duplex cord

 

 

 

 

 

Plastic fiber-optic,

50

1550

standard cable

 

 

 

 

 

PCF fiber-optic,

300

9300

standard cable

 

 

 

 

 

 

Table 3-8

Permitted Cable Lengths in an OLM Network

 

 

 

 

Fiber-optic cable

Maximum cable

For 1 Network (= 32

SIMATIC NET

lengths between two

nodes) (in m)

 

PROFIBUS

nodes (in m)

 

 

 

 

Plastic fiber-optic,

50

1550

duplex cord

 

 

 

 

 

Plastic fiber-optic,

80

2480

standard cable

 

 

 

 

 

PCF fiber-optic,

400

12400

standard cable

 

 

 

 

 

 

Note

SOptical buses can contain max. 32 integrated optical interfaces in series.

SSeveral buses of up to 32 integrated optical interfaces can only be linked via OBTs (optical repeaters).

SIn optical networks (bus, star, ring) containing only OLMs, the number of OLMs is limited to 122.

SThe number of all optical components (integrated interfaces, OBTs, OLMs) in the optical PROFIBUS network must be specified in the configuration tool as the “Number of OLM, OBT” parameter (see Section 3.3). This number must not exceed 122.

PROFIBUS Networks SIMATIC NET

3-17

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 83
Image 83