5 LED Indicators and Troubleshooting

5.1 LED Indicators

5LED Indicators and Troubleshooting

5.1LED Indicators

PROFIBUS OLM

LED indicators System

CH 2 CH 1 CH 2 CH 3

CH 3

Receive

Signal

Intensity

GND

Fig. 14: LED indicators on the front plate

LED Indicator

 

 

Possible causes

System

 lights green

– The transmission rate has been recognized and the power supply is in order

 

 not lit

– Power supply has failed (total failure*)

 

 

 

– Power supply connected incorrectly

 

 

 

– Module defective

 

 flashes red

Transmission rate has not yet been recognized

 

 

 

– No transmitting bus subscriber present

 

 

 

– No connection to a partner module sending frames

 

 

 

– Send and receive optical fibers have been transposed

 

 

 

– Transmission rate does not correspond to the PROFIBUS standard

 

 

 

– Only one active bus subscriber is connected, which is only sending tokens to

 

 

 

itself. The indicator must switch over after a second bus subscriber has been

 

 

 

activated (token frames on their own are not enough to set the transfer rate).

 

 

 

– The connected RS 485 segment is only terminated at one end.

 

 flashes red/green

Transmission rate recognized but

 

 

 

– the network slot time could not be determined (network parameter HSA is set

 

 

 

too low, no transmitting bus subscriber present)

 

 

 

– one optical port is set to ”Redundant optical ring“ mode, but not the second

 

 

 

(this operating mode must always be set at both optical ports)

 

 

 

– the slot time of the network configuration is too short

Signaling contact

no signal signal

no signal

no signal

* failure of both power supply sources with redundant infeed