Siemens SIMATIC NET PROFIBUS manual Technical Data of the 12M Bus Terminal, Climatic Conditions

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 159
Image 159

Passive Components for RS-485 Networks

4.7.7Technical Data of the 12M Bus Terminal

Technical Data of the 12M Bus Terminal

 

Connector to DTE

9-pin sub-D male connector

Transmission rate

9.6 Kbps to 12 Mbps

Power supply

DC 5 V ± 5%

 

safety extra-low voltage (SELV) complying with

 

EN 60950

Current consumption

90 mA at 5 V

Total power dissipation

0.45 W

Value factor

0.1

 

In operation at 1.5 Mbps along with

 

RS-485 bus terminal.

 

(See Section: “Network Configuration”)

Electromagnetic Compatibility

 

Noise emission

 

limit class

B complying with EN 55022=CISPR 22

Noise immunity on signal lines

+/– 2 kV (to IEC 801-5 / IEC 1000-4-5, surge)

 

+/– 2 kV (to IEC 801-4 / IEC 1000-4-4, burst)

Noise immunity to static electricity discharge

+/– 6 kV, contact discharge (to IEC 801-2; ESD /

 

IEC 1000-4-2)

Noise immunity to high-frequency interference

10 V/m with 80% amplitude modulation at

 

1 kHz,

 

80 MHz – 1 GHz (to IEC 801-3 / ENV 50140)

 

10 V/m 50 % on time at 900 MHz (to ENV

 

50204)

 

10 V with 80 % amplitude modulation at 1 kHz

 

10 kHz – 80 MHz (to IEC 801-6 / ENV 50141)

Climatic Conditions

 

Operating temperature

0 to 60 ° C

Storage/transport temperature

–40 to 70 ° C

Relative humidity

max. 95% at +25 ° C no condensation

PROFIBUS Networks SIMATIC NET

4-61

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 159
Image 159
Siemens SIMATIC NET PROFIBUS Technical Data of the 12M Bus Terminal, Electromagnetic Compatibility, Climatic Conditions