Siemens SIMATIC NET PROFIBUS manual Low Led

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 384
Image 384

Infrared Link Modul (ILM)

6ZB530–3AC30–0BA1

 

 

LED Display

 

Possible Causes

Signaling

 

 

 

Contact

 

 

 

 

POWER LED

lit green

- No acknowledgment pulse received since partner

Signals when

 

 

station not configured with acknowledgment pulse

configured

TX LED

lit orange,

- On point-to-multipoint links on the PROFIBUS

(acknowledg-

 

 

ment pulse)

 

 

ILM of the master subnet if acknowledgment bit

RX LED

lit yellow

 

configured (see Section 6.4)

 

 

 

 

 

 

 

 

POWER LED

lit green

- No acknowledgment pulse received since partner

Signals if

 

 

station is not configured with acknowledgment

 

TX LED

lit orange,

pulse or receive level for acknowledgment pulse

configured

 

 

and response frame too low.

 

RX LED

lit yellow,

- On a point-to-multipoint link on the PROFIBUS

(acknowledg-

 

 

ment pulse,

 

 

ILM on a slave subnet if configured with acknow-

LOW LED

lit red

ledgment bit (see Section 6.4)

level monito-

 

 

 

ring)

POWER LED

lit green

- Partner station not responding because not atta-

Signals when

 

 

ched, infrared link interrupted, incorrectly configu-

configured

TX LED

lit yellow

red (PROFIBUS address of the slave incorrect,

 

 

 

data rate of the partner PROFIBUS ILM set incor-

(bus activity)

RX LED

not lit

rectly etc.)

 

 

 

 

 

 

 

POWER LED

lit green

- Risk of problems on bus, since infrared link has

Signals when

 

 

too much attenuation (obstacles in area of trans-

configured

TX LED

lit yellow,

mission link, distance between PROFIBUS ILMs

 

 

 

too great, PROFIBUS ILM turned out of line with

(level monito-

RX LED

lit yellow,

partner station)

ring)

LOW LED

lit red

 

 

 

 

 

 

POWER LED

lit green

- Risk of problems on bus due to incidence of ex-

Signals when

 

 

traneous light (for example sunlight, lamps with

configured

TX and RX LEDs not lit

infrared component, halogen lamps with high

 

 

 

energy)

(constant

ERROR LED

lit red

 

light)

 

 

 

 

POWER LED

lit green

- Bus problems must be expected due to incidence

Signals when

 

 

of extraneous light with high-frequency modula-

configured

RX LED

lit yellow

tion (for example energy-saving lamps with HF

 

 

 

switching device)

(constant

ERROR LED

lit red

 

light)

Table 1:

Possible problems operating the PROFIBUS ILM

 

Copyright by Siemens

42

Page 384
Image 384
Siemens SIMATIC NET PROFIBUS manual Low Led