6ZB5530–3AC30–0BA1

Infrared Link Modul (ILM)

 

 

10 Help With Problems During Operation

10.1Status Displays for Incorrect Operation

LED Display

 

 

Possible Causes

Signaling

 

 

 

 

Contact

 

 

 

 

 

POWER LED

not lit

-

Power supply failed or turned off

Always si-

 

 

-

Module defective

gnals

 

 

 

 

 

- Ribbon band cable not plugged in when assem-

 

 

 

 

bling the module

 

 

 

 

 

 

POWER LED

lit green

-

Interruption on one or more cores of the RS 485

 

 

 

 

LAN cable

 

TX LED

not lit

- Reversed connection of core A and B of the RS

 

 

 

 

RX LED

not lit

 

485 LAN cable

 

- Connected PROFIBUS master defective (not sen-

 

 

 

 

 

 

 

ding)

 

 

 

- PROFIBUS node is not attached or attached

 

 

 

 

PROFIBUS node is not turned on

 

 

 

- No partner station detected with attached PROFI-

 

 

 

 

BUS master

 

 

 

 

 

 

POWER LED

lit green

-

Interruption on one or more cores of the RS 485

 

 

 

 

LAN cable

 

TX LED

not lit

- Reversed connection of core A and B of the RS

 

 

 

 

RX LED

lit yellow

 

485 LAN cable

 

- Attached PROFIBUS slave defective (not sen-

 

 

 

 

 

 

 

ding)

 

 

 

- PROFIBUS slave is not attached or attached

 

 

 

 

PROFIBUS slave is not turned on

 

 

 

- PROFIBUS slave node not correctly addressed

 

 

 

 

and therefore not responding

 

 

 

 

 

 

POWER LED

lit green

-

No acknowledgment pulse received, partner sta-

Signals when

 

 

 

tion not responding

configured

TX LED

lit orange,

 

 

(acknowledg-

 

 

 

 

ment pulse)

RX LED

not lit

 

 

 

41