Siemens SIMATIC NET PROFIBUS manual Status Displays for Incorrect Operation

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 383
Image 383

6ZB5530–3AC30–0BA1

Infrared Link Modul (ILM)

 

 

10 Help With Problems During Operation

10.1Status Displays for Incorrect Operation

LED Display

 

 

Possible Causes

Signaling

 

 

 

 

Contact

 

 

 

 

 

POWER LED

not lit

-

Power supply failed or turned off

Always si-

 

 

-

Module defective

gnals

 

 

 

 

 

- Ribbon band cable not plugged in when assem-

 

 

 

 

bling the module

 

 

 

 

 

 

POWER LED

lit green

-

Interruption on one or more cores of the RS 485

 

 

 

 

LAN cable

 

TX LED

not lit

- Reversed connection of core A and B of the RS

 

 

 

 

RX LED

not lit

 

485 LAN cable

 

- Connected PROFIBUS master defective (not sen-

 

 

 

 

 

 

 

ding)

 

 

 

- PROFIBUS node is not attached or attached

 

 

 

 

PROFIBUS node is not turned on

 

 

 

- No partner station detected with attached PROFI-

 

 

 

 

BUS master

 

 

 

 

 

 

POWER LED

lit green

-

Interruption on one or more cores of the RS 485

 

 

 

 

LAN cable

 

TX LED

not lit

- Reversed connection of core A and B of the RS

 

 

 

 

RX LED

lit yellow

 

485 LAN cable

 

- Attached PROFIBUS slave defective (not sen-

 

 

 

 

 

 

 

ding)

 

 

 

- PROFIBUS slave is not attached or attached

 

 

 

 

PROFIBUS slave is not turned on

 

 

 

- PROFIBUS slave node not correctly addressed

 

 

 

 

and therefore not responding

 

 

 

 

 

 

POWER LED

lit green

-

No acknowledgment pulse received, partner sta-

Signals when

 

 

 

tion not responding

configured

TX LED

lit orange,

 

 

(acknowledg-

 

 

 

 

ment pulse)

RX LED

not lit

 

 

 

41

Copyright by Siemens

Page 383
Image 383
Siemens SIMATIC NET PROFIBUS manual Status Displays for Incorrect Operation, LED Display Possible Causes Signaling Contact