Siemens SIMATIC NET PROFIBUS manual Redundant optical ring

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 409
Image 409

3 Network Topologies

3.2 Star topology

Switch on the terminating resistors in the bus port connectors (see 4.4.3, ”Connecting the electric RS 485 bus lines“, p. 22) at both ends of the electrical star segment.

Do not connect a bus subscriber to the electrical star segment wherever possible.

Modules with one or two optical ports can be used to create an active PROFIBUS star coupler. Modules with one optical port are sufficient for connecting a terminal or an RS 485 bus segment to the active star coupler.

If the link monitoring on the optical ports is activated, the fiber optic links are monitored by the respectively connected OLM.

Note:

Optical ports which are not assigned (for instance, because they are reserved for a future system extension) indicate a fiber break if the link monitoring is activated.

You can prevent this error report from being issued by activating the operating mode ”Line without fiber link monito- ring “ at the non-assigned ports.

Please note that optical ports which are not connected must always be fitted with protective caps to guard against extraneous light and dirt.

3.3 Redundant optical ring

R

T

R

T

CH 2

CH 3

OLM/P12

OLM/G12 (-1300)

CH 1

R

T

R

T

CH 2

CH 3

OLM/P12

OLM/G12 (-1300)

CH 1

R

T

R

T

CH 2

CH 3

OLM/P12

OLM/G12 (-1300)

CH 1

R

T

R

T

CH 2

CH 3

OLM/P12

OLM/G12 (-1300)

CH 1

RS 485 bus line

Optical fiber

Terminal unit /

Terminal unit /

Terminal unit /

Terminal unit /

bus segment

bus segment

bus segment

bus segment

Fig. 4: Network structure in a redundant optical ring topology

Version 1.0 8/00

13

Page 409
Image 409
Siemens SIMATIC NET PROFIBUS manual Redundant optical ring, Network structure in a redundant optical ring topology