6ZB5530–3AC30–0BA1

Infrared Link Modul (ILM)

 

 

6 Modes and Settings

To operate the PROFIBUS ILM, the terminating resistor, the data rate and the monitoring options must be set manually.

Note:

When shipped, the configuration is as follows:

âThe terminating resistor is inactive

âThe data rate is set to 1.5 Mbps

âThe “monitor link with acknowledgment pulse” monitoring mechanism is inactive.

âThe activation of the signaling contact is disabled.

The settings can be made after removing the cover from the basic module using switches S201 (transmission rate and monitoring mechanisms) and S202 (terminating resistor).

Terminating resistor switch

Configuration switch (S201)

(S202)

 

ON OFF

0

1

Plug connector for ribbon cable

1

1 Power supply and signaling contact

PROFIBUS attachments

Cable clamps for contacting the shield

PROFIBUS cable Cable for power supply and signaling contact

Figure 6: Elements for Setting the Configuration of the PROFIBUS ILM

21

Copyright by Siemens

Page 363
Image 363