Siemens SIMATIC NET PROFIBUS manual Point-to-Point-Link

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 353
Image 353

6ZB5530–3AC30–0BA1

Infrared Link Modul (ILM)

 

 

5.2.1PointtoPointLink

Slave

Infrared transmission link 0.5 to 15 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ILM

 

 

ILM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROFIBUS

PROFIBUS

master network segment

slave network segment

Master

Master

Figure 2: Point-to-Point Link with Two PROFIBUS ILMs

Slave

Slave

Slave

Figure 2 describes the typical layout of a PROFIBUS network with master and slave nodes and an infrared transmission link with two PROFIBUS ILMs. The infrared transmission link is implemented as a point-to-point link by the two PROFIBUS ILMs. In this situation, the two PROFIBUS ILMs replace a cable connection between the two network segments. Remember that only slave nodes are permitted in the slave network segments.

+Make sure that the terminating resistors are activated at the segment ends (either in the bus connector or in a PROFIBUS ILM).

Cascading is a further application for a point-to-point link.

Note

This “cascading with PROFIBUS ILM” mode is possible, but does involve a risk when operating PROFIBUS. The transmission using an infrared link is generally more susceptible to problems than transmission via cable (optical or electric).

11

Copyright by Siemens

Page 353
Image 353
Siemens SIMATIC NET PROFIBUS manual Point-to-Point-Link, Point-to-Point Link with Two Profibus ILMs Slave