6ZB5530–3AC30–0BA1

Infrared Link Modul (ILM)

 

 

5.2.1PointtoPointLink

Slave

Infrared transmission link 0.5 to 15 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ILM

 

 

ILM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROFIBUS

PROFIBUS

master network segment

slave network segment

Master

Master

Figure 2: Point-to-Point Link with Two PROFIBUS ILMs

Slave

Slave

Slave

Figure 2 describes the typical layout of a PROFIBUS network with master and slave nodes and an infrared transmission link with two PROFIBUS ILMs. The infrared transmission link is implemented as a point-to-point link by the two PROFIBUS ILMs. In this situation, the two PROFIBUS ILMs replace a cable connection between the two network segments. Remember that only slave nodes are permitted in the slave network segments.

+Make sure that the terminating resistors are activated at the segment ends (either in the bus connector or in a PROFIBUS ILM).

Cascading is a further application for a point-to-point link.

Note

This “cascading with PROFIBUS ILM” mode is possible, but does involve a risk when operating PROFIBUS. The transmission using an infrared link is generally more susceptible to problems than transmission via cable (optical or electric).