Passive Components for RS-485 Networks

Table 4-10 Pinout of the Sub D Connector

Pin

Signal

Meaning

 

 

 

1

PE

Protective earth

 

 

 

2

NC

Not used

 

 

 

3

B (RXD/TXD-P)

Data line B (receive/transmit data P)

 

 

 

4

NC

Not used

 

 

 

5

M5V2 (DGND)

Data ground

 

 

 

6

P5V2 (VP)

+ 5V voltage plus

 

 

 

7

NC

Not used

 

 

 

8

A (RXD/TXD-N)

Data line A (receive/transmit data N)

 

 

 

9

NC

Not used

 

 

 

4-50

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 148
Image 148
Siemens SIMATIC NET PROFIBUS manual Rxd/Txd-P