Configuring Networks

Table 3-5 Examples Illustrating the Configuration Rules

No special conditions if the length of the LAN cable

 

LAN cable > 10 m

between two DTEs > 10 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

> 10 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S7-400

S7-300

No special conditions if the length of the LAN ca-

Bus cable, e.g.

5 m

bles between two DTEs is greater than the sum of

V = 1.5 + 1.0 + 0.1 = 2.6

values of both DTEs.

5 m > 2.6 m (sum of the values in

 

If a bus terminal or a bus connector has a PG inter-

 

meters)

face, a connected PG connecting cable must be

S7-400

 

 

taken into account when calculating the values.

 

 

V = 1.0

 

 

 

 

5 m

 

V = 0.1

 

 

 

 

V = 1.5

 

 

 

 

S7-300

Take the values of a group into account if the sum

LAN cable e.g. 0.5 m group

of the values is greater than the LAN cable bet-

V = 1.5 + 1.5

 

ween the DTEs.

 

0.5 m < 3 m

group formed

Elements can be close to each other providing the

sum of the values 5

total value of a group does not exceed 5.

 

 

 

 

S7-400

S7-400

 

0.5 m

 

 

V = 1.5

 

V = 1.5

PROFIBUS Networks SIMATIC NET