Configuring Networks

Note

The slot time calculation takes into account only the optical network and the attachment of nodes to the OLM in each case via a maximum 20 m long RS-485 bus segment. Longer RS-485 bus segments must be included by adding them to the length FOC.

With the OLM/G11-1300 and OLM/G12-1300, the minimum slot times shown in the following table must be maintained at transmission rates of 12 Mbps, 6 Mbps, 3 Mbps and 1.5 Mbps.

Table 3-11 Minimum Slot Time for

OLM/G11-1300 and OLM/G12-1300

Transmission rate

 

Minimum slot

 

 

time

 

 

 

12

Mbps

3800 tBit

6

Mbps

2000 tBit

3

Mbps

1000 tBit

1.5

Mbps

530 tBit

When configuring the slot time, use the minimum slot time as shown in Table 3-11 if the calculated slot time is less than the minimum slot time.

Note

If the slot time is configured with a value that is too low, this can lead to malfunctions and error displays on the OLM. The system LED flashes red/green.

3.3.3Example of Configuring the Bus Parameters in STEP 7

Structure of the Network Example

The example assumes a redundant optical ring with the following structure:

S20 OLM G12 modules in the redundant optical ring

S20 km total ring length

STransmission Rate 1.5 Mbps

SNodes attached directly to OLMs

S“PROFIBUS-DP” bus protocol

3-30

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000