Siemens SIMATIC NET PROFIBUS manual Electromagnetic compatibility EMC, Climatic ambient conditions

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 428
Image 428

7

Technical Data

 

 

 

 

 

 

 

OLM Module

P11

G11

G11-1300

 

 

P12

G12

G12-1300

 

 

 

G12-EEC

 

 

 

 

 

Transmission distance

 

 

0 - 15000 m 2)

with glass fiber E 10/125

 

(0.5 dB/km)

 

0 - 3000 m 2)

0 - 10000 m

with glass fiber G 50/125

 

(860 nm: 3.0 dB/km; 1310 nm: 1.0 dB/km)

 

0 - 3000 m 2)

 

with glass fiber G 62,5/125

0 - 10000 m

 

(860 nm: 3.5 dB/km; 1310 nm: 1.0 dB/km)

 

 

 

– with PCF fiber S 200/230

 

 

 

 

Transmitting power ”Reduced“

 

Transmitting power ”Default“

0 - 400 m 2)

 

(660 nm: 10.0 dB/km; 860 nm: 8.0 dB/km)

 

 

 

– with plastic fiber S 980/1000

 

 

 

 

Transmitting power ”Reduced“

0 - 50 m

 

Transmitting power ”Default“

0 - 80 m

 

(0.25 dB/m)

 

 

 

Connector

BFOC/2.5

 

 

Electromagnetic compatibility (EMC)

 

 

 

 

 

 

Interference emissions

Limit class B (EN 55022)

 

 

 

Interference immunity against static charges

At shielded socket and housing parts: ±8 kV contact discharge

 

 

(EN 61000-4-2)

 

 

Immunity against high-frequency interference

– 10 V/m at 80% amplitude modulation with 1 kHz,

80 MHz - 1 GHz (EN 61000-4-3)

10 V/m at 50% on-period at 900 MHz (ENV 50204)

10 V/m at 80% amplitude modulation with 1 kHz,

10 kHz - 80 MHz

Immunity against line-conducted disturbance

On power supply lines and shielded

(Burst)

RS 485 bus lines: ±2 kV (EN 61000-4-4)

Immunity against line-conducted disturbance

– On power supply lines: ±1 kV symmetrical

(Surge)

– On shielded RS 485 bus lines: ±2 kV asymmetrical

 

(EN 61000-4-5)

Climatic ambient conditions

 

Ambient temperature

0 °C to +60 °C (IEC 68-2-1, IEC 68-2-2)

 

–20 °C to +60 °C at OLM/G12-EEC 1) (IEC 68-2-1, IEC 68-2-2)

Storage temperature

–40 °C to +70 °C (IEC 68-2-14)

Relative humidity

<95 %, non-condensing (IEC 68-2-30)

 

100 %, condensing at OLM/G12-EEC 1) (IEC 68-2-30)

Mechanical ambient conditions

 

Vibration (during operation)

10 to 58 Hz, 0.075 mm displacement;

 

58 to 150 Hz, 10 m/s2 (1 g) acceleration (IEC 68–2–6)

Vibration (during transport)

5 to 9 Hz, 3.5 mm displacement;

 

9 to 500 Hz, 10 m/s2 (1 g) acceleration

 

 

Protection class

IP 40

 

 

Dimensions (W x H x D)

39.5 x 110 x 73.2 mm

 

 

Housing material

Die-cast zinc

 

 

Weight

approx. 500 g

 

 

1)The OLM/G12 can also be supplied in a special design for more severe environmental conditions. This variant is designated the OLM/G12-EEC. The DIL switches on the OLM/G12-EEC may also only be operated at ambient temperatures between 0°C and + 60°C.

2)The specified distance allowed between two OLMs must not be exceeded regardeless of the optical power budget.

The module does not contain any silicon.

Version 1.0 8/00

32

Page 428
Image 428
Siemens SIMATIC NET PROFIBUS Electromagnetic compatibility EMC, Climatic ambient conditions, Mechanical ambient conditions