Siemens SIMATIC NET PROFIBUS manual SIENOPYR-FR Marine Cable 6XV1830-0MH10, Inner sheath

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 120
Image 120

Passive Components for RS-485 Networks

4.1.9SIENOPYR-FR Marine Cable

 

Inner sheath of

Cores, stranded copper

halogen-free

polymer

 

Dummy cores

Copper braid shield

 

 

Aluminum foil

Outer sheath of

halogen-free polymerCellular PE insulation

Figure 4-12 Structure of the SIENOPYR-FR Marine Cable

SIENOPYR-FR Marine Cable 6XV1830-0MH10

The SIENOPYR-FR marine cable meets the requirements of EN 50170, cable type A. The inner conductor consists of 7-strand copper (approximately 22 gauge). The outer sheath of cross-linked, halogen-free polymer is extremely resistant to lubricants and fuels, hydraulic fluid, cold cleansing agents and deionized water.

The outer sheath of the SIENOPYR-FR marine cable can be removed separately so that the inner sheath can be fitted into all PROFIBUS connectors with an 8 mm cable inlet.

The cable is not suitable for use of the FastConnect (FC) stripping tool.

Properties

The SIENOPYR-FR marine cable has the following properties:

SHalogen-free

SResistant to diesel fuel, ASTM oil, hydraulic fluid, cold cleansing agents, deionized water complying with VG 95 218 Part 2

SResistance to ozone complying with DIN VDE 0472 Part 805, test type B

SBurning behavior complying with DIN VDE 0472 Part 804, test type C

SCorrosivity of combustion gases complying with DIN VDE 0472 Part 813 (corresponds to IEC 60754-2)

SShip-building approvals (Germanischer Lloyd, Lloyd’s Register, Registro Italiano Navale)

4-22

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 120
Image 120
Siemens SIMATIC NET PROFIBUS manual SIENOPYR-FR Marine Cable 6XV1830-0MH10, Inner sheath