Configuration

 

 

 

6.2 Configuration of redundant optical rings

 

 

 

 

Data rate

a

b

c

 

12

MBit/s 1)

1651

240

28

 

6

MBit/s 1)

951

120

24

 

3

MBit/s 1)

551

60

24

 

1.5

MBit/s

351

30

24

 

500

kBit/s

251

10

24

 

187.5

kBit/s

171

3.75

24

 

93.75 kBit/s

171

1.875

24

 

45.45 kBit/s

851

0.909

24

 

19.2

kBit/s

171

0.384

24

 

9.6

kBit/s

171

0.192

24

 

 

 

Table 3a: Constants for calculating the slot time at DP standard

(redundant optical ring)

 

 

 

 

 

 

 

 

Data rate

a

b

c

 

12

MBit/s 1)

1651

240

28

 

6

MBit/s 1)

951

120

24

 

3

MBit/s 1)

551

60

24

 

1.5

MBit/s

2011

30

24

 

500

kBit/s

771

10

24

 

187.5

kBit/s

771

3.75

24

 

93.75 kBit/s

451

1.875

24

 

45.45 kBit/s

851

0.909

24

 

19.2

kBit/s

181

0.384

24

 

9.6

kBit/s

171

0.192

24

 

 

 

 

 

 

 

Table 3b: Constants for calculating the slot time at DP/FMS (”universal“) and DP with S5 95U (redundant optical ring)

The calculation of the slot time only takes into consideration the optical network and the connection of bus sub- scribers to the OLM via an RS 485 bus segment with a respctive length of max. 20 m. Longer RS 485 bus segments must be allowed for by adding them to the Length OF .

Note:

When the slot time is configured with a too small value the OLM will, through it’s fault function and fault indications, indicate such. The System-LED will blink red/green.

1)Using the OLM/G11-1300 and OLM/G12-1300 at data rates of 12 MBit/s, 6 MBit/s, 3 MBit/s and 1.5 MBit/s the minimum slot times according to the following table must be met.

Data rate

Minimum slot time

12

MBit/s

3800 tBit

6

MBit/s

2000 tBit

3

MBit/s

1000 tBit

1.5 MBit/s

530 tBit

 

Table 4: Minimum slot time on OLM/G11-1300 and

OLM/G12-1300

Use the values from Table 4 if the calculated slot time is smaller than the minimum slot time indicated in the table.

Version 1.0 8/00

30

Page 426
Image 426
Siemens SIMATIC NET PROFIBUS manual Constants for calculating the slot time at DP standard