Configuring Networks

Calculation of the Slot Time

For the transmission rates of 1.5 Mbps selected in the example, Table 3-9 lists the following values

a = 351 b = 30 c = 24

On this basis, the slot time is calculated as follows:

Slot time = 351 + (30 x 20) + (24 x 20) = 1431

Entering the Bus Parameters

This means that the following three bus parameters must be entered for the example:

Slot time (T_slot_Init)

=

1431

Retries (Retry_Limit)

=

3

Highest station address (HSA)

=

126 (default)

These values are entered in STEP 7 in the “Bus Parameters” dialog for the “User-Defined” bus profile.

You must then trigger the recalculation of the bus parameters with the “Recalculate” button.