Technical Specifications

7

Table 7-1 Technical Specifications

Technical Specifications

Power supply (safety extra–low voltage with reliable isolation, SELV or complying with NEC Class 2)

Power consumption at 24 V input

Transmission rate

Transmission rate setting

Mode

Bit error rate

Input channel 1 to channel 3

Bit length

Jitter

Output channel 1 to 3

Bit length

Jitter

24 VDC (18 V to 32 V)

max. 200 mA

12 Mbps, 6 Mbps, 3 Mbps, 1.5 Mbps, 500 Kbps, 187.5 Kbps , 93.75 Kbps, 45.45 Kbps, 19.2 Kbps, 9.6 Kbps

made automatically

optical bus

<10–9

0.7 to 1.3 tBit

-0.03 to +0.03 tBit

0.99 to 1.01 tBit

-0.003 to +0.003 tBit

Signal delay time (any input/output)

6 tBit

 

 

 

Cascading depth of optical bus

limited only by signal run time

 

 

 

Electrical channel

 

 

 

 

 

Input/output signal

RS–485 level

 

 

 

 

Input dielectric strength

-7 V to +12 V

 

 

 

 

Minimum current at 5V (for terminating resistors)

10 mA

 

 

 

Electrical isolation from 24V input

Isolation due to function; not safety–related!

 

 

 

Optical channels

 

 

 

 

 

Optical source

LED

 

 

 

 

Coupled optical power

PT(min)

PT(max)

– in plastic fiber 980/1000

– 5.9 dBm

+0.5 dBm

– in PCF fiber 200/230

– 16 dBm

–1.5 dBm

 

 

 

Receiver sensitivity

PR(min)

PR(max)

– with plastic fiber 980/1000

–20 dBm

0 dBm

– with PCF fiber 200/230

–22 dBm

–2 dBm

 

 

 

PROFIBUS Optical Bus Terminal (OBT)

7-1

C79000-G8976-C122-02

Page 461
Image 461
Siemens SIMATIC NET PROFIBUS manual Technical Specifications