Testing PROFIBUS

A.2.4 Checking the Optical Signal Quality with PROFIBUS OLM V3

The receive level of the two optical channels can be detected using a normal commercially available voltmeter attached to measurement sockets on the PROFIBUS OLM V3. The voltmeter can be inserted and removed during operation using 2 mm laboratory test plugs (see Figure A-6).

Figure A-6 Testing the Signal Quality on an OLM V3 with a Voltmeter

This allows the following:

SThe incoming optical power can be documented, for example for later measurements (aging, damage)

SA good/bad check can be made (limit value).

The correlation between the measured output voltage and the signal quality is in the form of a curve (see Figure A-7).

A-12

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000