Passive Components for RS-485 Networks

Disconnecting a Station

The bus connector allows you to disconnect a node from the bus without interrupting the data traffic on the bus.

Removing the bus connector when the terminating resistor is activated at the end of the cable causes disruptions on the bus and is not permitted.

Bus Connector with PG Socket

We recommend that you include at least one bus connector with a PG socket in each bus segment. This makes it easier to commission using a programming device or PC.

In the bus connectors with a PG socket, all the contacts are connected 1:1 with the connector pins; in other words, the pinout is the same as the pinout of the attached device.

Pinout of the Sub-D male Connector

Table 4-8 shows the pinout of the 9-pin sub-D male connector.

Table 4-8 Pinout of the 9-pin Sub-D Male Connector

Pin

Signal

Meaning

no.

name

 

 

 

 

1

-

-

 

 

 

2

-

-

 

 

 

3

RxD/TxD-P

Data line B

 

 

 

4

-

-

 

 

 

5

M5V2

Data reference potential (from station)

 

 

 

6

P5V2

Power supply plus (from station)

 

 

 

7

-

-

 

 

 

8

RxD/TxD-N

Data line A

 

 

 

9

-

-

 

 

 

4-36

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 134
Image 134