Siemens SIMATIC NET PROFIBUS manual 10.0 dB, 12 dB

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 86
Image 86
= 1310 nm

Configuring Networks

Power Budget for OLM G11-1300, G12-1300 for One Point-to-Point Link at Wavelength λ

Attenuation on the cable

Fiber type

Attenuation

Cable length

 

aFOC

L

62.5/125 m

1.0 dB/km

9 km

 

 

 

Attenuation for connectors

 

 

 

 

aConn

Number

 

1 dB

0

 

 

 

 

Attenuation caused by splices

 

 

 

 

aSpl

Number

 

0.2 dB

5

 

 

 

 

Attenuation of the transmission path

Data of the OLM/G11-1300, G12-1300 power that can be coupled into 62.5/125 m fibers

Pout, min

–17 dBm

Receiver sensitivity

Prec, min

–29 dBm

Maximum permitted attenuation

Link power margin

L* aFOC =

 

9.0 dB

 

+

 

 

+

 

 

 

 

Number *

 

0 dB

aConn

 

 

 

+

 

 

 

 

Number * aSpl

 

1.0 dB

 

 

 

aPath =

 

10.0 dB

amax = Pout, min – Prec, min =

12 dB

amax – aPath =

2 dB

The transmission path can be implemented as planned.

Note

The maximum length of fiber-optic cable that can be supplied in one piece depends on the cable type but is approximately 3 km per drum. Longer links must therefore be put together using more than one piece of cable. To connect the sections of cable, coupling elements or splices must be used reducing the maximum possible cable length due to their attenuation.

3-20

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 86
Image 86
Siemens SIMATIC NET PROFIBUS manual 10.0 dB, 12 dB