Siemens SIMATIC NET PROFIBUS manual Screw M6 x By turning

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 377
Image 377

6ZB5530–3AC30–0BA1

Infrared Link Modul (ILM)

 

 

 

Alignment

Screw M6 x 16

by turning

ILM

Mounting bracket 1

Mounting bracket 2

Installation site

Installing the ILM with mounting bracket side view

Threaded cable inlets

Cables for

PROFIBUS, power supply and signaling contact

Figure 15: Side View of a PROFIBUS ILM Installed With Mounting Brackets

By installing angle 1 in different holes on the mounting surface, it is possible to turn the PROFIBUS ILM through the vertical axis, however the adjustment is not continuous.

By loosening the M6 securing bolts, the PROFIBUS ILM can be adjusted continuously to align it to the partner station in the horizontal axis. To add greater stability, it is advisable to use toothed washers with the bolts.

It is also advisable to install the module at the edge of the mounting surface so that the cables lead to and from the module unhindered and to make sure that there is no reflection of the sender to its own receiver caused by the installation site itself.

35

Copyright by Siemens

Page 377
Image 377