Active Components for RS-485 Networks

Technical Specifications

Table 5-2 lists the technical data of the RS-485 repeater:

Table 5-2 Technical Data of the RS-485 Repeater

Technical Specifications

Power supply

 

S

Rated voltage

24 V DC

 

 

 

S

Ripple (static limit)

20.4 V DC to 28.8 V DC

 

 

Power consumption at rated voltage

 

 

 

S Without load on the PG/OP connector

200 mA

 

 

S Load on the PG/OP connector (5 V/90 mA)

230 mA

 

 

S Load on the PG/OP connector (24 V/100 mA)

300 mA

 

 

Electrical isolation

yes, 500 V AC

 

 

Transmission rate (detected automatically by

9.6 Kbps, 19.2 Kbps, 45.45 Kbps,

repeater)

93.75 Kbps, 187.5 Kbps, 500 Kbps,

 

 

1.5 Mbps, 3 Mbps, 6 Mbps 12 Mbps

 

 

Degree of protection

IP20

 

 

Dimensions W H D (in mm)

45 128 67

 

 

Weight (including packing)

350 g

 

 

 

Pinout of the Sub D Connector (PG/OP Connector)

The 9-pin sub D connector has the following pinout:

Table 5-3 Pin Assignment of the 9-Pin Sub D Connector PG/OP Connector

Layout

Pin no.

Signal name

Meaning

1

5

 

4

9

 

3

8

7

 

2

6

1

 

2

M24V

Chassis 24 V

 

 

 

3

RxD/TxD-P

Data line B

 

 

 

4

RTS

Request To Send

 

 

 

5

M5V2

Data reference potential (from station)

 

 

 

6

P5V2

Power supply plus (from station)

 

 

 

7

P24V

24 V

 

 

 

8

RxD/TxD-N

Data line A

 

 

 

9

 

 

 

5-4

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000