Active Components for RS-485 Networks

Connecting the PROFIBUS Cable

Connect the PROFIBUS LAN cable to the PROFIBUS terminator, as follows:

1.Cut the PROFIBUS cable to the required length.

2.Strip the insulation from the PROFIBUS cable as shown in Figure 5-10.

The braid shield must be folded back on to the cable. Only then can the shield clamp serve as strain relief and as the shield contact.

e.g. standard cable

 

6XV1 830-0EH10

 

8,5

16

10

e.g. underground cable

 

 

6XV1 830-3FH10

 

 

16

16

10

8,5

 

 

Braid shield must be folded back!

Figure 5-10 Stripping the Insulation to Connect to the PROFIBUS Terminator

3.Connect the PROFIBUS LAN cable to the PROFIBUS terminator:

Connect the same wires (green/red for the PROFIBUS LAN cable) to the same terminal A or B (in other words always connect terminal A with a green wire and terminal B with a red wire or vice versa).

4.Tighten the shield clamps so that the shield makes good contact with the clamp.

Note

When installing the segment, make sure that no terminating resistor is activated on the bus connectors if the two PROFIBUS terminators are included in the PROFIBUS segment.

PROFIBUS Networks SIMATIC NET

5-17

6GK1970-5CA20-0AA1 Release 2 05/2000