Siemens SIMATIC NET PROFIBUS manual Using the FastConnect Stripping Tool for Preparing FC Cables

Models: SIMATIC NET PROFIBUS

1 490
Download 490 pages 10.94 Kb
Page 128
Image 128

Passive Components for RS-485 Networks

4.2.3Using the FastConnect Stripping Tool for Preparing FC Cables

The steps required to strip a cable are illustrated using the using the FastConnect bus connector with a 90° cable outlet 6ES7972-0BB50-0XA0.

They apply analogously to the FastConnect bus connector with a 180° cable outlet 6GK1500-0FC00.

1.How to hold the stripping tool in the right hand

2.Measure the length to be stripped by holding the cable against the template. Mark the position using the index finger of your left hand.

3.Insert the measured end of the cable into the tool as far as allowed by the index finger of the left hand.

4.Clamp the end of the cable in the stripping tool.

5.Turn the tool four times in the direction of the arrow for PVC insulation (eight times for PUR or PE insulation).

6.Keeping the tool closed, remove it from the end of the cable. If the cut is poor, change the blade cassette.

7. Remnants remain in the

8. Remove the protective

9. Fit the FastConnect cable

tool. After opening the tool,

layer from the cores.

into the connector.

the remnants of the cable can

 

 

be removed.

 

 

4-30

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

Page 128
Image 128
Siemens SIMATIC NET PROFIBUS manual Using the FastConnect Stripping Tool for Preparing FC Cables