5.Be sure that hub flanges, flex members, spacer, and hard- ware are clean and free of oil.

6.Place the flanges onto the shafts with the hub facing out- ward. Do not tighten the set screws at this time.

7.Outside of the unit, assemble the flex members to the cen- ter drive shaft with 4 bolts and nuts. The flex members have collars that need to be inserted into the smaller hole of the drive shaft flange.

8.Assemble the flex member/drive shaft assembly to one of the shaft flanges, using 2 bolts and nuts. Slide the other shaft flange towards the assembly and assemble using 2 bolts and nuts. If the shafts are not misaligned, the collar in the flex member should line up with the shaft flange holes.

9.Torque nuts properly to 95 to 100 ft-lb. Do not turn a cou- pling bolt. Always turn the nut. Always use thread lubri- cant or anti-seize compound to prevent thread galling.

10.The ends of the shafts should be flush with the inside of the shaft flange. Torque the set screws to 25 ft-lb.

11.After assembly is complete, slowly rotate the shafts by hand for 30 to 60 seconds.

12.Tighten the bearing mounting bolts, using care not to place any loads on the shaft which would cause flexure to the shafts.

13.Reinstall drive belts. (Refer to Belt Tension Adjustment section below.)

14.Visually inspect the assembly. If the shafts are overly mis- aligned, the drive shaft flange will not be parallel with the shaft flanges.

15.Recheck nut torque after 1 to 2 hours of operation. Bolts tend to relax after being initially torqued.

Evaporator Fan Service and Replacement

1.Turn off unit power supply.

2.Remove supply-air section panels.

3.Remove belt and blower pulley.

4.Loosen setscrews in blower wheels.

5.Remove locking collars from bearings.

6.Remove shaft.

7.Remove venturi on opposite side of bearing.

8.Lift out wheel.

9.Reverse above procedure to reinstall fan.

10.Check and adjust belt tension as necessary.

11.Restore power to unit.

Belt Tension Adjustment — To adjust belt tension:

1.Turn off unit power supply.

2.Loosen motor mounting nuts and bolts. See Fig. 69.

3.Loosen fan motor nuts.

4.Turn motor jacking bolts to move motor mounting plate left or right for proper belt tension. A slight bow should be present in the belt on the slack side of the drive while running under full load.

5.Tighten nuts.

6.Adjust bolts and nut on mounting plate to secure motor in fixed position. Recheck belt tension after 24 hours of operation. Adjust as necessary. See Table 3 for proper tension values.

7.Restore power to unit.

Evaporator-Fan Motor Replacement

1.Turn off unit power supply.

2.Remove upper outside panel and open hinged door to gain access to motor.

3.Fully retract motor plate adjusting bolts.

4.Loosen the 2 rear (nearest the evaporator coil) motor plate nuts.

5.Remove the 2 front motor plate nuts and carriage bolts.

6.Slide motor plate to the rear (toward the coil) and remove fan belt(s).

7.Slide motor plate to the front and hand tighten one of the rear motor plate nuts (tight enough to prevent the motor plate from sliding back but loose enough to allow the plate to pivot upward).

8.Pivot the front of the motor plate upward enough to allow access to the motor mounting hex bolts and secure in place by inserting a prop.

9.Remove the nuts from the motor mounting hex bolts and remove motor.

10.Reverse above steps to install new motor.

Condenser-Fan Adjustment

1.Turn off unit power supply.

2.Remove fan guard.

3.Loosen fan hub setscrews.

4.Adjust fan height on shaft using a straightedge placed across venturi and measure per Fig. 70.

5.Fill hub recess with permagum if rubber hubcap is missing.

6.Tighten setscrews and replace panel(s).

7.Turn on unit power.

Fig. 69 — Belt Tension Adjustment

Fig. 70 — Condenser-Fan Adjustment

92

Page 92
Image 92
Carrier 48EK, 48EW, 48EY024-068, 48AW Evaporator Fan Service and Replacement, Belt Tension Adjustment To adjust belt tension

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.