NOTES:
1.Weights include economizer (standard).
2. Center of Gravity.
3.Do not locate adjacent units with flue discharge facing econo- mizer inlet.
Min Clearances to be:
Adjacent Units:
Top of Units: No Overhang.
Condenser Coil:
Economizer Side:
Heat Side:
Filter Access Side:
4.For smaller service and operational clearances contact Carrier Application Engineering Department.
5.Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts must be supported by cross braces as done on accessory roof curb.
6.Base unit weights include outdoor air hoods and filters (indoor fan motor is not included). Add indoor motor, FIOPs and acces- sories for total operating weight.
7.VAV motor weights include indoor motor, VFD, compressor electric unloaders, VFD transducer and associated wiring.
8.Dimensions in are in inches [mm].
15
BASE UNIT WEIGHTS (See Note 6) lbs (kg)
|
|
| 054 | 058 |
| 064 | 068 |
| |||
| 48EJD/EKD | 6805 (3087) | 7055 (3200) |
| 7305 (3314) | 7480 (3393) | |||||
|
| 48EJE | 7045 (3196) | 7295 (3309) |
| 7545 (3422) | 7720 (3502) | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CENTER OF GRAVITY | % OF TOTAL WEIGHT | ||||||
UNIT SIZE | Inches | Millimeters | AT EACH CORNER | |||||
| A | B | A | B | 1 | 2 | 3 | 4 |
48EJD/EKD054 | 130.9 | 46.9 | 3325 | 1192 | 22.4 | 19.6 | 27.0 | 30.9 |
48EJE054 | 133.8 | 47.4 | 3397 | 1204 | 23.1 | 19.8 | 26.3 | 30.7 |
48EJD/EKD058 | 132.1 | 47.5 | 3354 | 1207 | 22.9 | 19.5 | 26.5 | 31.1 |
48EJE058 | 139.5 | 49.6 | 3544 | 1260 | 25.3 | 19.6 | 24.1 | 31.1 |
48EJD/EKD064 | 125.3 | 45.2 | 3181 | 1149 | 20.7 | 19.6 | 29.1 | 30.7 |
48EJE064 | 132.2 | 47.2 | 3359 | 1199 | 22.8 | 19.7 | 26.7 | 30.8 |
48EJD/EKD068 | 127.7 | 46.6 | 3242 | 1184 | 21.7 | 19.3 | 27.7 | 31.2 |
48EJE068 | 134.7 | 48.6 | 3422 | 1235 | 23.9 | 19.4 | 25.4 | 31.3 |