Carrier 48EW, 48AW Pressure Transducer Locations, 48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 54
Image 54
Fig. 51 — Pressure Transducer Locations

NOTES:

1.Unless otherwise specified, all dimensions are to outside of part.

2.Dimensions are in inches.

3.On 48AW,AY and 48EW,EY units, accessory barometric relief or power exhaust must be mounted in the field-supplied return ductwork.

Fig. 50 — Barometric Relief Damper and Power Exhaust Mounting Details

LEGEND

VAV — Variable Air Volume

Fig. 51 — Pressure Transducer Locations

(48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068)

Step 12 — Install All Accessories — After all the factory-installed options have been adjusted, install all field-in- stalled accessories. Refer to the accessory installation instruc- tions included with each accessory.

MOTORMASTER® III CONTROL INSTALLATION

Install Field-Fabricated Wind Baffles — Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low-ambient temperatures. See Fig. 52 for baffle details. Use 20-gage, galvanized sheet metal, or similar corro- sion-resistant metal for baffles. Use field-supplied screws to at- tach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Holes for wind baffles are pre-punched in the unit sheet metal.

To avoid damage to the refrigerant coils and electrical com- ponents, use recommended screw sizes only.

The wind baffles attach to flanges formed on the outer sheet metal of the unit corner post. The other end of the baffle is at- tached to the center panel between the condenser coil and the indoor section. Two baffles are required.

54

Page 54
Image 54
Carrier 48EW, 48EY024-068, 48AW, 48AY020-060 Pressure Transducer Locations, 48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068