Filter Drier — Replace whenever refrigerant system is ex- posed to atmosphere.

Protective Devices

COMPRESSOR PROTECTION

Overcurrent — Each compressor has one manual reset, cali- brated trip, magnetic circuit breaker. Do not bypass connec- tions or increase the size of the circuit breaker to correct trou- ble. Determine the cause and correct it before resetting the breaker.

Overtemperature — Each 06D type compressor (48AJ,AK, AW,AY020-035 and 48EJ,EK,EW,EY024-038 units only) has an internal protector to protect it against excessively high dis- charge gas temperatures.

Crankcase Heater — Each compressor has a crankcase heater to prevent absorption of liquid refrigerant by oil in the crank- case when the compressor is idle. Since power for the crank- case heaters is drawn from the unit incoming power, main unit power must be on for the heaters to be energized.

IMPORTANT: After a prolonged shutdown or service job, energize the crankcase heaters for 24 hours before starting the compressors.

EVAPORATOR FAN MOTOR PROTECTION — A manu- al reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker. If the evaporator-fan motor is replaced with a different horsepower motor, resizing of the circuit breaker is required. Contact Carrier Application Engineering.

CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature.

HIGH- AND LOW-PRESSURE SWITCHES — If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automatically locked out. See Compressor Lockout Logic section on this page.

FREEZE PROTECTION THERMOSTAT (FPT) — Freeze protection thermostats are located on the evaporator coil for each circuit. One is located at the top and bottom of each coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized.

Relief Devices — All units have relief devices to protect against damage from excessive pressures (i.e., fire). These de- vices are installed on the suction line, liquid line, and on the compressor.

Power Circuit — A typical power wiring schematic is shown in Fig. 77.

Control Circuit, 24-VThis control circuit is protect- ed against overcurrent by a 3.2 amp circuit breaker (CB4). Breaker can be reset. If it trips, determine cause of trouble be- fore resetting. A typical 24-v control wiring schematic is shown in Fig. 78 and 79.

Control Circuit, 115-VThis control circuit is pro- tected against overcurrent by a 5.2 amp circuit breaker (CB3). Breaker can be reset. If it trips, determine cause of trouble be- fore resetting. A typical 115-v control wiring schematic is shown in Fig. 80 and 81.

Compressor Lockout Logic — If any of the safeties trip, the circuit will automatically reset (providing the safety has reset) and restart the compressor in 15 minutes. If any of the safeties trip 3 times within a 90-minute period, then the cir- cuit will be locked out and will require manual resetting by turning off either the unit disconnect or the control circuit breaker, or opening the thermostat.

If the compressors have bee off for more than 15 minutes and the outdoor-air temperature (OAT) is less than 45 F then safeties will be ignored for 5 minutes.

Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request.

LEGEND for Fig. 77-83 — Typical Wiring Schematics

 

 

 

LEGEND

AFS

Airflow Switch

HTSASP — Heating Supply Air Set Point

AHA

Adjustable Heat Anticipator

 

Potentiometer

BP

Building Pressure

HV

High Voltage

BR

Burner Relay

IDM

Induced-Draft Motor

C

Contactor, Compressor

IFC

Indoor Fan Contactor

CAP

Capacitor

IFCB

Indoor Fan Circuit Breaker

CB

Circuit Breaker

IFM

Indoor-Fan Motor

CC

Cooling Compensator

IFR

Indoor-Fan Relay

CCB

Controller Circuit Breaker

IGC

Integrated Gas Unit Controller

CCH

Crankcase Heater

IP

Internal Protector

CLSASP — Cooling Supply Air

L

Light

 

Set Point Potentiometer

LPS

Low-Pressure Switch

COM

Communication

LS

Limit Switch

COMP

Compressor Motor

MGV

Main Gas Valve

CR

Control Relay

NC

Normally Closed

CV

Constant Volume

NO

Normally Open

DM

Damper Motor

OAT

Outdoor-Air Thermostat

DP

Duct Pressure

OD

Outdoor

EC

Enthalpy Control

OFC

Outdoor-Fan Contactor

FLA

Full Load Amps

OFM

Outdoor-Fan Motor

FPT

Freeze Protection Thermostat

PEC

Power Exhaust Contactor

FU

Fuse

PEM

Power Exhaust Motor

GVR

Gas Valve Relay

PES

Power Exhaust Sequencer

HPS

High-Pressure Switch

PESC

Power Exhaust Sequencer Controller

HS

Hall Effect Sensor

PL

Plug Assembly

RAT

Return-Air Thermistor

RS

Rollout Switch

SAT

Supply-Air Thermostat

SEN

Sensor

SW

Switch

TB

Terminal Block

TC

Thermostat, Cooling

TH

Thermostat, Heating

TRAN — Transformer

UL

Compressor Unloader

VFD

Variable Frequency Drive

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Factory Wiring

Field Wiring

To indicate common potential only. Not to represent wiring.

95

Page 95
Image 95
Carrier 48EJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48AJ specifications Protective Devices

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.