Carrier 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48EJ Base Unit Dimensions — 48AJ,AK035-050

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 8
Image 8
Fig. 6 — Base Unit Dimensions — 48AJ,AK035-050

NOTES:

 

 

 

OPERATING

 

 

CORNER WEIGHT (lbs)

1.

Weights include economizer (standard).

UNIT SIZE

A

B

 

 

 

 

WEIGHT*

(ft-in.)

(ft-in.)

1

2

3

4

2.

Center of Gravity.

 

(lbs)

 

 

 

48AJ/AK (Low Heat) 035

6004

7-811/16

3-107/8

1380

1209

1595

1820

3.

Do not locate adjacent units with flue discharge facing economizer

 

inlet.

 

 

48AJ (High Heat) 035

6164

7-101/8

3-113/16

1447

1251

1607

1859

 

Min Clearances to be:

48AJ/AK (Low Heat) 040

6514

7-55/16

3-107/8

1442

1264

1779

2030

 

Adjacent Units: 15-0[4572].

48AJ (High Heat) 040

6674

7-613/16

3-113/16

1512

1307

1787

2068

 

Top of Units: No Overhang.

 

Condenser Coil: 4-0[1219].

48AJ/AK (Low Heat) 050

6725

7-311/16

3-101/2

1449

1294

1878

2104

 

Economizer Side: 6-0[1829].

48AJ (High Heat) 050

6885

7-53/16

3-1013/16

1519

1337

1886

2142

 

[1219].

 

Heat Side: 4 -0

 

 

 

 

 

 

 

 

 

 

Filter Access Side: 10-0[3048]. (For removal of evaporator coil.)

 

 

 

 

 

 

 

 

4.

For smaller service and operational clearances contact Carrier Appli-

 

OPERATING

 

 

 

 

 

 

5.

cation Engineering Department.

UNIT SIZE

A (mm)

B (mm)

CORNER WEIGHT (kg)

Bottom ducts designed to be attached to accessory roof curb. If unit is

WEIGHT*

1

2

3

4

 

mounted on dunnage, it is recommended the ducts must be supported

 

(kg)

 

 

 

by cross braces as done on accessory roof curb.

48AJ/AK (Low Heat) 035

2723

2355

1191

626

548

723

826

6.

Dimensions are in inches [mm].

48AJ (High Heat) 035

2796

2390

1199

656

567

729

843

 

 

 

 

 

 

 

 

48AJ/AK (Low Heat) 040

2955

2268

1191

654

573

807

921

 

 

 

 

48AJ (High Heat) 040

3027

2306

1199

686

593

811

938

 

 

 

 

48AJ/AK (Low Heat) 050

3050

2228

1181

657

587

852

954

 

 

 

 

48AJ (High Heat) 050

3123

2266

1189

689

607

856

972

8

Fig. 6 — Base Unit Dimensions — 48AJ,AK035-050

Page 8
Image 8
Carrier 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48EJ specifications Base Unit Dimensions — 48AJ,AK035-050