Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AJ Navigator Display Menu Structure

Models: 48EJ 48AJ 48AK 48EK 48AY020-060 48AW 48EY024-068 48EW

1 118
Download 118 pages 46.64 Kb
Page 85
Image 85
Fig. 60 — Navigator Display

 

 

M O

D E

 

 

Run

Status

 

 

S

 

 

 

 

 

 

 

 

ervice

Test

 

 

Tem

 

 

 

 

peratures

 

 

Pre

 

 

 

 

 

 

 

ssures

 

 

 

Setpoints

 

 

 

Inputs

 

 

 

 

Ou

 

 

 

 

Co

tputs

 

 

 

 

 

 

 

 

 

nfigu

 

 

 

 

 

ration

 

 

Time

 

 

 

O

Clock

 

 

 

 

pera

 

 

 

A

larms

ting M

odes

 

 

 

 

 

 

C o

 

 

 

 

m

 

 

 

 

f o

 

 

 

N A

r t

L i

n k

V I G A

 

 

T O

 

 

 

R ™

Alarm

Status

 

E S C

NOTE: To utilize Morning Warm-Up mode, the unit occu- pancy schedule must be accessed via Service Tool, Building Supervisor, or ComfortWORKS® software or accessory Remote Enhanced Display. The PC can access the base control board via the 3-wire communication bus or via an RJ-11 con- nection to the CCN terminal on the base control board. See Fig. 27.

For current software (version 3.0 or later), the Low Tem- perature Minimum Damper Position Override (LOWMDP) has a 0 to 100% limit, with a default of 100%. Think of the LOWMDP as a second minimum damper position. This LOWMDP limit change requires access to the unit software

ENTER

Fig. 60 — Navigator Display

MORNING WARM-UP (VAV only with PC Accessed/CCN Operation) — Morning warm-up occurs when the control has been programmed to turn on heat prior to the Occupied mode to be ready for occupancy mode. Morning warm-up is a condi- tion in VAV systems that occurs when the Temperature Com- pensated Start algorithm calculates a biased occupied start time and the unit has a demand for heating. The warm-up will con- tinue into the occupied period as long as there is a need for heat. During warm-up, the unit can continue heating into the occupied period, even if occupied heating is disabled. When the heating demand is satisfied, the warm-up condition will ter- minate. To increase or decrease the heating demand, use Service Tool software to change the Occupied Heating set point.

with a computer equipped with Building Supervisor, Ser- vice Tool, or ComfortWORKS Software.

When the LOWMDP is in effect the outdoor dampers will remain at the LOWMDP position (typically set to 0% closed) during heating, even in the Occupied period. For the LOW- MDP to be in effect the LOWMDP must be less than the mini- mum damper position (MDP) and the RAT (return-air tempera- ture) must be less than the OHSP (occupied heat set point) minus 2.5° F. Table 40 summarizes the operational require- ments and controlling factors for occupied heat and morning warm-up.

MORNING WARM-UP (VAV Only with Stand-Alone Operation) — When the unit operates in stand-alone mode, morning warm-up occurs when the unit is energized in Occu- pied mode and return-air temperature (RAT) is below 68 F. Warm-up will not terminate until the RAT reaches 68 F. The heat interlock relay output is energized during morning warm- up. (A field-installed 24-vdc heat interlock relay is required.) The output will be energized until the morning warm-up cycle is complete. Refer to Fig. 59 for heat interlock relay wiring.

Table 39 — Navigator Display Menu Structure

RUN

SERVICE

TEMPERATURES

PRESSURES

SET

INPUTS

OUTPUTS

CONFIGURATION

TIME CLOCK

OPERATING

ALARMS

STATUS

TEST

 

 

POINTS

 

 

 

 

MODES

 

 

 

 

 

 

 

HEAT

Display

 

 

Currently

Auto Display

SERVICE

SUPPLY AIR

 

SETPOINT

COOL

Time

 

Active

N/A

OUTPUT

Configuration

N/A

(VIEW)

TEST

TEMPERATURE

SELECT

INPUT#1

(TIME)

Alarms

 

1

(DISP)

 

 

 

 

 

 

 

 

 

(CRNT)

 

 

 

 

 

 

 

 

 

 

Software

 

 

 

COOLING

 

HEAT

CCN

 

 

Reset all

HEAT

SUPPLY AIR

 

COOL

Date

 

Current

Version

N/A

SETPOINT

OUTPUT

Configuration

N/A

OUTPUT#1

TEMPERATURE 1

INPUT#2

(DATE)

Alarms

(VERS)

 

 

 

1

 

2

(CCN)

 

 

(RCRN)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Occupancy

 

 

 

 

 

 

COOLING

 

HEAT

Stage Gas

and

 

Alarm

 

HEAT

SUPPLY AIR

 

HEAT

Unoccupancy

 

 

N/A

SETPOINT

OUTPUT

Configuration

 

History

 

OUTPUT#2

TEMPERATURE 2

INPUT#1

Schedule

 

 

 

 

 

2

 

3

(CNFG)

Number

 

(HIST)

 

 

 

 

 

 

 

 

(SCHD)

 

 

 

 

 

 

HEATING

 

HEAT

 

 

 

Reset

 

HEAT

SUPPLY AIR

 

HEAT

 

 

 

Alarm

 

 

SETPOINT

OUTPUT

 

 

 

 

OUTPUT#3

TEMPERATURE 3

 

INPUT#1

 

 

 

History

 

 

 

 

1

 

4

 

 

 

(RHIS)

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

 

HEATING

SUPPLY

HEAT

 

 

 

 

 

 

 

SETPOINT

FAN

OUTPUT

 

 

 

 

 

OUTPUT#4

 

 

 

 

 

 

 

 

 

2

STATUS

5

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

 

OUTPUT#5

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

 

 

OUTPUT#6

 

 

 

 

 

 

 

 

 

85

Page 85
Image 85
Carrier 48AK, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AJ, 48EJ specifications Navigator Display Menu Structure