Table 41 — Smoke Control Modes
DEVICE | PRESSURIZATION | SMOKE PURGE | EVACUATION | FIRE SHUTDOWN |
Economizer | 100% | 100% | 100% | 0% |
Indoor Fan/VFD | ON | ON | OFF | OFF |
Power Exhaust (all outputs) | OFF | ON | ON | OFF |
Heat Stages | OFF | OFF | OFF | OFF |
Cool Stages | OFF | OFF | OFF | OFF |
HIR | ON | ON | OFF | OFF |
LEGEND |
|
|
|
|
HIR — Heat Interlock Relay |
|
|
|
|
VFD — Variable Frequency Drive |
|
|
|
|
HEAD PRESSURE CONTROL — Each unit has a fan cy- cling, outdoor thermostat to shut off the
MOTORMASTER® III CONTROL — The Motormaster III
CAPACITY CONTROL, COOLING — The cooling capaci- ty staging tables are shown in Tables 42 and 43.
Table 42 — Cooling Capacity Staging Table, CV
Units with 2 Compressors
|
| Stages |
|
|
| 0 | 1 | 2 | 3 |
| Economizer | |||
|
|
|
| |
Compressor 1 | off | off | on | on |
Compressor 2 | off | off | off | on |
NOTE: On CV units that require additional unloading, add suction pressure unloaders to Compressor 1 only.
Table 43 — Cooling Capacity Staging Table VAV Units with 2 Compressors and 2 Unloaders*
|
|
|
| STAGES |
|
|
| ||
| 0 | 1 | 2 |
| 3 |
| 4 | 5 | 6 |
Compressor 1 | off | on | on |
| on |
| on | on | on |
Unloader 1 | off | on | on |
| off |
| on | on | off |
Unloader 2 | off | on | off |
| off |
| on | off | off |
Compressor 2 | off | off | off |
| off |
| on | on | on |
*40 ton units have only one unloader.
It is often desirable to use a variable air volume (VAV) unit in a variable volume and temperature (VVT) control system because of the greater unloading capability. A VAV unit (with software version 4.0 and later) can easily be configured in the field to run off of either space thermostat (VVT® relay pack) input or a space sensor. When configured in this manner, the unit control will turn on compressors based upon load in the space. If the
A VAV unit configured to run off thermostat input or a space sensor will have the capability for two stages of heating, however, modification to the control wiring will be required to make this available. The Variable Frequency Drive (VFD) for the supply fan will still be active, varying the supply air fan speed to maintain supply duct pressure.
Upon a call for Y1 (or Y2_SPT) cooling, the compressor 1 will start after appropriate Time Guard® functions. Thirty sec- onds after the SAT drops below the “SAT1TRIP” the compres- sor will be unloaded. The unloading sequence will be as follows:
Compressor no. 1 | On, Full Load | Unloader no. 1 and no. 2 Off |
Compressor no. 1 | On, 2/3 Load | Unloader no. 1 Off, Unloader no. 2 On |
Compressor no. 1 | On, 1/3 Load | Unloader no. 1 and no. 2 On |
Compressor no. 1 | Off | Unloader no. 1 and no. 2 Off |
The “Y1 Low SAT Limit” has an adjustable range from
50 F to 65 F, with a factory setting of 53 F. If the temperature of the SAT rise above the “Y1 Low SAT Limit” plus 2° F, the compressor will be loaded in the reverse order in which it was unloaded following the
If compressor no. 1 is forced off due to “Y1 LOW SAT Limit” an alert will be issued. If economizer is suitable, the economizer mode will remain active. The alert will be cleared after the
Upon a call for Y1 (or Y1_SPT) and Y2 (or Y2_SPT) cool- ing both compressor no. 1 and 2 will start after appropriate time guards. Thirty seconds after SAT drops below the “Y2 Low SAT Limit” the compressor will be unloaded. The unloading sequence will be as follows:
Compressor no. 1 | Unloader no. 1 and no. 2 Off | Compressor no. 2 On | |
On, Full Load |
|
|
|
Compressor no. 1 | Unloader no. 1 | Off, | Compressor no. 2 On |
On, 2/3 Load | Unloader no. 2 | On |
|
Compressor no. 1 | Unloader no. 1 and no. 2 On | Compressor no. 2 On | |
On, 1/3 Load |
|
|
|
Compressor no. 1 | Unloader no. 1 and no. 2 Off | Compressor no. 2 Off | |
On, Full Load |
|
|
|
Compressor no. 1 | Unloader no. 1 | Off, | Compressor no. 2 Off |
On, 2/3 Load | Unloader no. 2 | On |
|
Compressor no. 1 | Unloader no. 1 and no. 2 On | Compressor no. 2 Off | |
On, 1/3 Load |
|
|
|
Compressor no. 1 Off | Unloader no. 1 and no. 2 Off | Compressor no. 2 Off |
The “Y2 Low SAT Limit” has an adjustable range from
45 F to 55 F, with a factory default setting of 48 F. If the tem- perature of the SAT rise above the “Y2 Low SAT Limit” plus 2° F, the compressor will be loaded in the reverse order in which it was unloaded following the
88