Cisco SFS 3012R Multifabric Server Switch Hardware Installation Guide
OL-11187-01
Chapter3 Installing and Removing Server Switch Field Replaceable Units (FRUs)
Installing a Power Supply Module
To insert a power supply, perform the following steps:
Step1 Ground yourself using an approved ground wrist strap.
Step2 Remove the blanking panel if one resides in the slot.
Step3 Remove the power supply module from any packaging.
Step4 Insert the power supply into an open slot such that the pull handle sits toward the outside of the chassis,
away from the blower module. The arrow on top of the power supply or underneath the power supply
must always point to the outside of the chassis.
Note The power supplies should be inserted in opposite directions of each other.
Step5 Press the power supply firmly into the chassis.
Note The power socket on the back (cable end) of the Cisco SFS 3012R Server Switch corresponds to
the power supply module on the same side of the server switch.