7.2 Programming Worksheets

[005] System Times

Valid entries for Entry Delay are between 030-255, valid entries for SIA CP-01 Exit Delay is between 045-255.

030

I___I___I___I

Entry Delay 1

045

I_0_I_3_I_0_I

Entry Delay 2

120

I_0_I_6_I_0_I

Exit Delay

004

I___I___I___I

Bell Cut-off

For SIA CP-01 compliant installations, the Exit Delay must be within the range of 045-255 seconds

(Default 60 seconds). If the Exit Delay is silent (Section 14, Option 6 or Stay Function Key Arming) the exit delay must be twice the programmed value but must not exceed 255 seconds (i.e., 090-255 seconds).

For UL Installations, the Entry Delay plus the Communications Delay must not exceed 60 seconds.

[006] Installer’s Code

[007] Master Code

 

 

 

Default

Default

 

 

 

 

5555

I I I I I

1234

I I I

I I

 

 

Programmable Output Options

 

 

 

 

 

00

Null PGM (Not Used)

 

 

10

System Event Output (with Event Options)

01

Residential Burglary and Fire Bell Output

 

 

11

System Tamper (all sources: zones, keypad)

02-04

Future Use

 

 

12

TLM and Alarm

 

05

System Armed Status

 

 

13-16

Future Use

 

06

Ready To Arm

 

 

17

Away Armed Status

 

07

Keypad Buzzer Follower

 

 

18

Stay Armed Status

 

08

Courtesy Pulse

 

 

19

Command Output #1 ([

][7][1])

09

System Trouble Output (with Trouble Options)

 

20

Command Output #2 ([

][7][2])

[009] I/O Programming

Program Zone Definition Attributes in Sections [133-134], Program PGM Option Attributes in sections [501] - [502]

Default

00

00

I I I

I I I

I/O Type (Zone 33, PGM 1)

Enter Zone Definition or PGM Definition

I/O Type (Zone 34, PGM 2)

Enter Zone Definition or PGM Definition

[012] Keypad Lockout Options

If Keypad Lockout is active, the panel cannot be disarmed with a keyswitch.

Default

000

000

I I I I

I I I I

Number of Invalid Codes Before Lockout

(Valid entries are 000-255)

Lockout Duration (in minutes)

(Valid entries are 000-255)

[013] First System Options

Opt

Def. ON

OFF

1

Hardwired Zone 33 Input Enabled

PGM1 Output Enabled

2

Hardwired Zone 34 Input Enabled

PGM2 Output Enabled

3-5

Future Use

 

6

Audible Exit Fault Enabled

Audible Exit Fault Disabled

7

Event Buffer follows Swinger Shutdown

Event Buffer Logs Past Shutdown

8

Temporal Three Fire Signal Enabled

Standard Pulsed Fire Signal

WWW.DIYALARMFORUM.COM17