Appendix E:
Appendix E: 2-Way Audio Verification (SCW9047 only)
The following information is intended for use by the Central Station Operator.
The SCW9047 Audio Verification provides Talk and
SIA Audio Verification Standard (November 11, 1997)
The 2-way Audio Session
1.Zone Violation: A
•Fire Zones, zone 87, 88, 89 and the Fire Key
•Supervisory zones, zones 9 and 10
•24 Hr Freeze zone, zone 20
By default
•Silent Panic events (Silent [P], Silent Panic zone)
•Duress alarm
•Silent zone alarm (Zone attribute 1 OFF)
NOTE: The Operator can NOT switch to Talk mode (Speaker is always OFF)
2.Communication to the Monitoring Station: When the appropriate Alarm is triggered one of the following reporting codes/actions is sent to the monitoring station.
Format | Reporting Code/Event |
|
|
SIA | L90 |
|
|
Contact ID | 606 |
|
|
BPS | Communicates the Event, then automatically enters into |
|
|
3.Alerting the Operator: When the reporting code is received by the monitoring station or a
2-way Initiation (Start) Tone:
3 Hi Tones (Short) | After the third short Hi tone has sounded, the system switches directly into |
| a keypress from the monitoring station. |
|
|
Reminder Tones: |
|
|
|
1 Hi Tone (Short) | 1 Short Hi Tone indicates 20 seconds are left in the audio session |
|
|
1 low Tone | 1 Short Low Tone indicates 10 seconds are left in the audio session |
|
|
Subsequent Alarm: |
|
|
|
1 Hi Tone Long | 1 long Hi Tone indicates a new alarm event if Section [023] Option 6 (New Alarms will not discon- |
| nect |
| NOTE: Receiving a subsequent alarm event tone will not restart the 90 second session timer. |
|
|
Subsequent Fire Event: | |
|
|
Hi, Low, Hi | 3 short (100ms) tones Hi, Low, Hi indicates a new Fire alarm if Section [023] Option 6 (New Alarms |
(Short) | will not disconnect |
| NOTE: Receiving a subsequent Fire alarm event tone will not restart the 90 second session timer. |
|
|
WWW.DIYALARMFORUM.COM57