Appendix C: Regulatory Approvals Information

Self Contained Wireless Alarm System v1.0

Appendix C: Regulatory Approvals Information

North America

This product has been tested and found in compliance with the following standards: UL1023 Household Burglar-Alarm System Units

UL985 Household Fire Warning System Units UL1635 Digital Alarm Communicator System Units

ULC-S545-02Residential Fire Warning System Control Units ORD-C1023-1974Household Burglar-Alarm System Units

This product has also been tested and found in compliance with the ANSI/SIA CP-01-2000 Control Panel Standard – Features for False Alarm Reduction.

This product is UL/ULC listed under the following categories: UTOU/UTOUC Control Units and Accessories, Household System Type NBSX/NBSXC Household Burglar Alarm System Units

AMTB Control Panels, SIA False Alarm Reduction

The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified in accordance with SIA-CP-01 Stan- dard) as proof of compliance with the above mentioned standards. For further information on this product’s listings please also refer to the official listing guides published at the UL web site (www.ul.com) under Certifications Section.

UL/ULC Residential Fire and Burglary Installations:

For ULC Installations refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.

All burglary-type zones shall be configured with SEOL or DEOL configuration (refer to section [133] and [134], bit 15 or 16 shall be ON)

Use at least one WS4916 Smoke Detector for Fire Installations (refer to section [001], fire zone shall be programmed as type 89)

The entry delay shall not exceed 60 seconds (refer to section [005])

The exit delay shall not exceed 120 seconds (refer to section [005])

The minimum Bell Time-out is 4 minutes (refer to section [005])

Note: For ULC Residential Fire Installations the minimum Bell Time-out is 5 minutes

Temporal Three Fire Signal shall be enabled (refer to section [013], option 8 shall be ON)

Arm/Disarm Bell Squawk shall be enabled when using wireless key WS4939 (refer to section [014], option 1 shall be ON)

Auxiliary Power boost shall be enabled (refer to section [014], option 4 shall be ON)

A code shall be required for bypassing (refer to section [015], option 5 shall be ON)

Trouble beeps shall be enabled (refer to section [023], option 7 shall be ON)

AC trouble indication LED shall be enabled (refer to Keypad Programming, section [075], options 5 and 6 shall be ON)

DACT Communicator shall be enabled for Supervising Station Monitoring (refer to section [380], option 1 shall be ON).

Note: The DACT communicator for this product has no line security.

Telephone Line Monitoring (TLM) shall be enabled (refer to section [015], option 7 shall be ON)

Note: This product is programmed to perform 5 attempts for communication of an event to the supervising station. If unsuccessful, a Fail To Communicate (FTC) trouble is generated.

Test transmission cycle shall be set for monthly transmission (refer to section [377])

Note: For ULC Residential installations set for daily test transmission

Wireless Supervision window shall be enabled (refer to Wireless Programming, sections [82] to [85])

Wireless Supervision window shall be set to 4h for Fire Installations (refer to Wireless Programming, section [81] shall be programmed with the value [16]

Wireless Supervision window shall be set to 24h for Burglary Installations only (refer to Wireless Programming, section [81] shall be programmed with the value [96]

RF Jam detection shall be enabled (refer to Wireless Programming, section [90], option 7 shall be OFF)

Bells will be active During 2-way Audio (refer to section [600], opt 7 shall be ON)

New Alarms will Disconnect 2-way Audio (refer to section [023], opt 6 shall be OFF)

When the 2- way audio feature is enabled (section [381] option 5 is ON) ensure that section [023] option 6 is OFF and section [600] option 7 is ON

Programming

The notes in the programming sections describing the system configurations for UL/ULC listed installations shall be implemented

Bell Location

The alarm sounding device (bell) shall be located where it can be heard by the person operating the security system during the daily arming and disarming cycle.

Casual Users

The installer should caution the user(s) not to give system information (e.g. codes, bypass methods, etc.) to casual users (baby-sitters or service people). Only the One-Time Use codes shall be given to casual users.

User Information

The installer should advise the users and note in the User’s Manual:

Service organization name and telephone number

The programmed exit time

The programmed entry time

Test system weekly