K

Keypad Alarm Shunting

Reference Topics:

Both Read/Keypad Type Reader

Keypad Only Type Reader

Normal Type Reader

The keypad alarm shunting feature allows you to turn the monitoring of a group of alarms off or on using the keypad. This can also be accomplished by setting up a schedule for an alarm group using a time schedule.

Only reader board door inputs and 20DI board input points can be shunted from a keypad.

To identify a reader board door input, look for a default description that follows this format: 0001-1-01 Reader.

To identify a 20DI board input point, look for a default description that follows this format: 0001-1-01 DI.

Keypad Only Type Reader

Only reader board door inputs and 20DI board input points can be shunted from a keypad. (To identify a reader board door input, look for a default description that follows this format: 01-1-01 Reader. To identify a 20DI board input point, look for a default description that follows this format: 01-1-01 DI.)

Follow the steps below to shunt alarm groups within a micro connected to a keypad reader.

1.Click the start key on the keypad. The start key is labeled with either an asterisk <*> or a plus <+> depending on the reader model.

2.Type one of the following:

0- to turn monitoring off

1- to turn monitoring on

3.Type the alarm group number (00 to 15) you want shunted.

4.Click the end key that is labeled with either a pound sign (#) or an <x>.

5.Click the start key on the keypad again.

6.Type your badge number on the keypad.

7.Click the end key (<#> or <x>).

Secure Perfect 6.1.1 User Manual

191

Page 193
Image 193
GE v6 user manual Keypad Alarm Shunting, Keypad Only Type Reader