3–32

“C” Group: Intelligent Terminal Functions

“C” Group: Intelligent Terminal Functions

The five input terminals [1], [2], [3], [4], and [5] can be configured for any of fifteen different functions. The next two tables show how to configure the five terminals. The inputs are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1.

The inverter comes with default options for the five terminals. These default settings are initially unique, each one having its own setting. Note that European and US versions have different default settings. You can use any option on any terminal, and even use the same option twice to create a logical OR (though usually not required).

NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a thermistor device when the PTC function (option code 19) is assigned to that terminal.

Configuring

Drive Parameters

 

 

Input Terminal Configuration

Functions and Options –The function codes in the following table let you assign one of fifteen options to any of the five logic inputs for the L100 inverters. The functions C_01through C_05 configure the terminals [1] through [5] respectively. The “value” of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options.

For example, if you set function C_01=00, you have assigned option 00 (Forward Run) to terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Func.

Name /

 

Description

Mode

–FE

–FU

–FR

Units

 

Edit

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_01

Terminal [1] function

Select function for terminal [1]

00

00

00

 

 

 

15 options (see next section)

 

[FW]

[FW]

[FW]

 

 

IN-TM 1

FW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_02

Terminal [2] function

Select function for terminal [2]

01

01

01

 

 

 

15 options (see next section)

 

[RV]

[RV]

[RV]

 

 

IN-TM 2

RV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_03

Terminal [3] function

Select function for terminal [3]

02

16

02

 

 

 

15 options (see next section)

 

[CF1]

[AT]

[CF1]

 

 

IN-TM 3

AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_04

Terminal [4] function

Select function for terminal [4]

03

13

03

 

 

 

15 options (see next section)

 

[CF2]

[USP]

[CF2]

 

 

IN-TM 4

USP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C_05

Terminal [5] function

Select function for terminal [5]

18

18

18

 

 

 

16 options (see next section)

 

[RS]

[RS]

[RS]

 

 

IN-TM 5

2CH