3–37

L100 Inverter

Output Function Summary Table – This table shows all six functions for the logical outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 4–21.

 

 

Output Function Summary Table

 

 

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

 

Description

 

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

RUN

Run Signal

ON

when inverter is in Run Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

when inverter is in Stop Mode

 

 

 

 

 

 

 

 

 

 

 

01

FA1

Frequency Arrival

ON

when output to motor is at the set frequency

 

 

 

 

 

Type 1 – Constant

 

 

 

 

 

 

 

OFF

when output to motor is OFF, or in any accelera-

 

 

 

 

 

Speed

 

 

 

 

 

 

tion or deceleration ramp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

FA2

Frequency Arrival

ON

when output to motor is at or above the set

 

 

 

 

 

Type 2 – Over-

 

frequency, even if in accel. or decel. ramps

 

 

 

 

 

frequency

 

 

 

 

 

 

 

OFF

when output to motor is OFF, or at a level below

 

 

 

 

 

 

 

 

 

 

 

 

 

the set frequency

 

 

 

 

 

 

 

 

 

 

 

03

OL

Overload Advance

ON

when output current is more than the set thresh-

 

 

 

 

 

 

 

Notice Signal

 

old for the overload signal

 

ParametersDrive

 

 

 

 

 

 

 

 

 

 

 

OFF

when output current is less than the set threshold

 

Configuring

 

 

 

 

for the overload signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

OD

Output Deviation for

ON

when PID error is more than the set threshold for

 

 

 

 

 

PID Control

 

the deviation signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

when PID error is less than the set threshold for

 

 

 

 

 

 

 

the deviation signal

 

 

 

 

 

 

 

 

 

 

 

05

AL

Alarm Signal

ON

when an alarm signal has occurred and has not

 

 

 

 

 

 

 

been cleared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

when no alarm has occurred since the last

 

 

 

 

 

 

 

clearing of alarm(s)