3–27

L100 Inverter

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Func.

Name /

 

Description

Mode

–FE

–FU

–FR

Units

 

Edit

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_31

Software lock mode

Prevents parameter changes, in

01

01

01

 

selection

 

four options, option codes:

 

 

 

 

 

 

 

 

00 ...all parameters except

 

 

 

 

 

 

S-LOCK

MD1

 

 

 

 

 

 

B_31 are locked when [SFT]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal is ON

 

 

 

 

 

 

 

 

01 ...all parameters except

 

 

 

 

 

 

 

 

B_31 and output frequency

 

 

 

 

 

 

 

 

F01 when SFT from terminal is

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

02 ...all parameters except

 

 

 

 

 

 

 

 

B_31 are locked

 

 

 

 

 

 

 

 

03 ...all parameters except

 

 

 

 

 

 

 

 

B_31 and output frequency

 

 

 

 

 

 

 

 

F_01 setting are locked

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: To disable parameter editing when using B_31 lock modes 00 and 01, assign the [SFT] function to one of the intelligent input terminals.

See “Software Lock” on page 4–17.

Parameters Drive

Configuring