3–38

“C” Group: Intelligent Terminal Functions

Analog Function Summary Table – This table shows all three functions for the analog output [FM] (frequency meter) terminal. Detailed descriptions, related parameters and settings, and example wiring diagrams are in “Analog and Digital Monitor Output” on page 4–30.

Analog Function Summary Table

Option

Function Name

Description

Code

 

 

 

 

 

 

 

 

00

Analog Frequency

PWM (pulse-width-modulated) voltage output that has a

 

Monitor

duty cycle proportional to the inverter output frequency

 

 

 

01

Analog Current Output

PWM (pulse-width-modulated) voltage output that has a

 

Monitor

duty cycle proportional to the inverter output current to the

 

 

motor. It reaches 100% duty cycle when the output

 

 

reaches 200% of the rated inverter current.

 

 

 

02

Digital Frequency

FM (frequency-modulated) voltage output with a constant

 

Output Monitor

50% duty cycle. Its frequency = inverter output frequency.

 

 

 

Configuring

Drive Parameters