External TripWhen the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of the error depends on what you connect to the [EXT] terminal. Even if the [EXT] input is turned OFF, the inverter remains in the trip state. You must reset the inverter or cycle power to clear the error, returning the inverter to the Stop Mode.
In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter lets the motor
[EXT] terminal | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
0 |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
| 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| free run |
| |||||
Motor revolution speed | 0 |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| ||
| 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
[RS] terminal | 0 |
|
|
|
|
|
|
|
|
|
|
Alarm output terminal | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
0 |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
RUN command [FW, RV] | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
0 |
|
|
|
|
|
|
|
|
|
|
t
Option | Terminal | Function Name | Input |
|
| Description |
|
|
|
|
|
| ||||
Code | Symbol | State |
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
12 | EXT | External Trip | ON | When assigned input transitions OFF to ON, | ||||||||||||
|
|
|
| inverter latches trip event and displays E12 | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| OFF | No trip event for ON to OFF, any recorded trip | ||||||||||||
|
|
|
| events remain in history until Reset |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C_01, C_02, C_03, C_04, | Example (requires input configuration— | ||||||||||||||
C_05 |
| |||||||||||||||
|
|
| see page |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Required settings: | (none) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| EXT |
|
|
|
| ||
Notes: |
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
| L | 5 | 4 | 3 |
| 2 |
| 1 | P24 |
| |||
• If the USP (Unattended Start Protection) feature is |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
in use, the inverter will not automatically restart |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
after cancelling the EXT trip event. In that case, it |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
must receive either another Run command (OFF- |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
[RS] intelligent terminal input signal. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| See I/O specs on page |
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operations Monitoring and