3–29

L100 Inverter

NOTE: When DC braking is performed, the inverter automatically holds the carrier frequency at 1 kHz.

NOTE: The carrier frequency setting must stay within specified limits for inverter- motor applications that must comply with particular regulatory agencies. For example, a European CE-approved application requires the inverter carrier to be less than 5 kHz.

B_84, B_85: Initialization codes – These functions allow you to restore the factory default settings. Please refer to “Restoring Factory Default Settings” on page 6–8.

B_86: Frequency display scaling – You can convert the output frequency monitor on D_01 to a scaled number (engineering units) monitored at function D_07. For example, the motor may run a conveyor that is monitored in feet per minute. Use this formula:

Scaled output frequency (D_07) = Output frequency (D_01) ⋅ Factor (B_86)

 

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FE

–FU

–FR

Units

 

 

 

Edit

 

 

 

Code

SRW Display

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring ParametersDrive

 

 

 

 

 

 

 

 

 

B_32

Reactive current setting

Calibrate detection of motor’s

58% rated current

A

 

 

 

 

 

no load (reactive) current to

 

 

 

 

 

 

 

 

IO 0.00A

 

 

 

 

 

 

 

 

 

 

improve D_02 display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

accuracy, range is 0 to 32

 

 

 

 

 

 

 

 

 

 

 

Amperes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_81

[FM] terminal analog

Adjust 8-bit gain to analog

80

80

80

 

 

 

 

meter adjustment

meter connected to terminal

 

 

 

 

 

 

 

 

 

 

 

[FM], range is 0 to 255

 

 

 

 

 

 

 

 

 

ADJ

080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_82

Start frequency adjust-

Sets the starting frequency for

0.5

0.5

0.5

Hz

 

 

 

 

 

 

ment

 

the inverter output, range is 0.5

 

 

 

 

 

 

 

 

 

 

 

to 9.9 Hz

 

 

 

 

 

 

 

 

 

Fmin

0.5Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_83

Carrier frequency

Sets the PWM carrier (internal

5.0

5.0

12.0

kHz

 

 

 

 

setting

 

switching frequency), range is

 

 

 

 

 

 

 

 

 

 

 

0.5 to 16.0 kHz

 

 

 

 

 

 

 

 

 

CARRIER

05.0kHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_84

Initialization mode

Select the type of initialization

00

00

00

 

 

 

 

(parameters or trip

to occur, two option codes:

 

 

 

 

 

 

 

 

 

history)

 

00 ...Trip history clear

 

 

 

 

 

 

 

 

 

 

 

01 ...Parameter initialization

 

 

 

 

 

 

 

 

 

INIT MODE

TRP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_85

Country code for initial-

Select default parameter values

01

02

00

 

 

 

 

ization

 

for country on initialization,

 

 

 

 

 

 

 

 

 

 

 

four options, option codes:

 

 

 

 

 

 

 

 

 

INIT SEL

USA

 

 

 

 

 

 

 

 

 

00 ...Japan version

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 ...Europe version

 

 

 

 

 

 

 

 

 

 

 

02 ...US version

 

 

 

 

 

 

 

 

 

 

 

03 ...reserved (do not set)