6–3

L100 Inverter

Troubleshooting Tips

The table below lists typical symptoms and the corresponding solution(s).

Symptom/condition

Probable Cause

Solution

 

 

 

 

 

 

 

 

 

 

Is the frequency command source

Make sure the parameter

 

 

A_01 parameter setting correct?

setting A_01 is correct.

 

 

Is the Run command source A_02

Make sure the parameter

 

 

parameter setting correct?

setting A_02 is correct.

 

 

 

 

 

 

Is power being supplied to termi-

Check terminals [L1], [L2],

 

 

nals [L1], [L2], and [L3/N]? If so,

and [L3/N], then [U/T1],

 

 

the POWER lamp should be ON.

[V/T2], and [W/T3].

 

 

 

Turn ON the power supply

 

 

 

or check fuses.

 

 

 

 

 

 

Is there an error code E X X

Press the Func. key and

 

The inverter

displayed?

determine the error type.

 

 

Eliminate the error cause,

 

outputs [U], [V],

 

then clear the error (Reset).

 

[W] are not

 

 

 

Are the signals to the intelligent

Verify the terminal functions

 

supplying

 

input terminals correct?

for C_01 – C_05 are correct.

 

voltage.

 

Is the Run Command active?

Turn ON Run Command

The motor

 

 

Is the [FW] terminal (or [RV])

enable.

will not run.

 

 

connected to [P24] (via switch,

Supply 24V to [FW] or [RV]

 

 

 

 

etc.)

terminal, if configured.

 

 

 

 

 

 

Has the frequency setting for F_01

Set the parameter for F_01

 

 

been set greater than zero?

to a safe, non-zero value.

 

 

Are the control circuit terminals

If the potentiometer is the

 

 

[H], [O], and [L] connected to the

frequency setting source,

 

 

potentiometer?

verify voltage at [O] > 0V.

 

 

 

 

 

 

Is the RS (reset) function or FRS

Turn OFF the command(s).

 

 

(free-run stop) function ON?

 

 

 

 

 

 

Inverter outputs

Is the motor load too heavy?

Reduce load, and test the

 

[U], [V], [W]

 

motor independently.

 

are supplying

 

 

 

voltage.

 

 

 

 

 

 

 

The optional

Are the operational settings

Check the operator type

 

remote operator

between the remote operator and

setting.

 

is used (SRW).

the inverter unit correct?

 

 

 

 

 

 

 

Are the connections of output

Make connections according

 

 

terminals [U/T1], [V/T2], and

to the phase sequence of the

 

 

[W/T3] correct?

motor. In general:

 

 

Is the phase sequence of the motor

FWD = U-V-W, and

The direction of the motor is

forward or reverse with respect to

REV=U-W-V.

 

[U/T1], [V/T2], and [W/T3]?

 

reversed.

 

 

 

 

 

Are the control terminals [FW] and

Use terminal [FW] for

 

 

[RV] wired correctly?

forward, and [RV] for

 

 

Is parameter F_04 properly set?

reverse.

 

 

 

Set motor direction in F_04.

 

 

 

 

Troubleshooting Maintenance and