Monitoring Trip Events, History, & Conditions
Troubleshooting and Maintenance
Error | Name | Cause(s) | |
Code | |||
|
| ||
|
|
| |
|
|
| |
E 1 2 | External trip | A signal on an intelligent input terminal configured as | |
| EXT has occurred. The inverter trips and turns OFF | ||
|
| ||
|
| the output to the motor. | |
|
|
| |
E 1 3 | USP | When the Unattended Start Protection (USP) is | |
| enabled, an error occurred when power is applied | ||
|
| ||
|
| while a Run signal is present. The inverter trips and | |
|
| does not go into Run Mode until the error is cleared. | |
|
|
| |
E 1 4 | Ground fault | The inverter is protected by the detection of ground | |
| faults between the inverter output and the motor | ||
|
| ||
|
| during powerup tests. This feature protects the | |
|
| inverter, and does not protect humans. | |
|
|
| |
E 1 5 | Input | When the input voltage is higher than the specified | |
| value, it is detected 100 seconds after powerup and | ||
|
| ||
|
| the inverter trips and turns OFF its output. | |
|
|
| |
E 2 1 | Inverter thermal trip | When the inverter internal temperature is above the | |
| threshold, the thermal sensor in the inverter module | ||
|
| ||
|
| detects the excessive temperature of the power | |
|
| devices and trips, turning the inverter output OFF. | |
|
|
| |
E 3 5 | Thermistor | When a thermistor is connected to terminals [5] and | |
| [CM1] and the inverter has sensed the temperature is | ||
|
| ||
|
| too high, the inverter trips and turns OFF the output. | |
|
|
| |
- - - U | Due to low input voltage, the inverter turns its output | ||
| out) with output shutoff | OFF and tries to restart. If it fails to restart, then the | |
|
| alarm trips to record the | |
|
|
|
NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still correct. If the power is turned OFF while the [RS] (Reset) intelligent input terminal is ON, an EEPROM error will occur when power is restored.