L100 Inverter

Overload Restriction

If the inverter’s output current exceeds a preset current level you specify during acceleration or constant speed, the overload restriction feature automatically reduces the output frequency to restrict the overload. This feature does not generate an alarm or trip event. You can instruct the inverter to apply overload restriction only during constant speed, thus allowing higher currents for acceleration. Or, you may use the same threshold for both acceleration and constant speed. In the case of controlled deceleration, the inverter monitors both output current and DC bus voltage. The inverter will increase output frequency to try to avoid a trip due to over-current or over-voltage (due to regeneration).

Motor

Current

Restriction area

B 22

0

t

Output

frequency

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

B 23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the inverter detects an overload, it must decelerate the motor to reduce the current until it is less than the threshold. You can choose the rate of deceleration that the inverter uses to lower the output current.

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Func.

Name /

 

Description

Mode

–FE

–FU

–FR

Units

 

Edit

Code

SRW Display

 

(CE)

(UL)

(Jpn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_21

Overload restriction

 

Select the operating mode

01

01

01

 

operation mode

 

during overload conditions,

 

 

 

 

 

 

 

 

three options, option codes:

 

 

 

 

 

 

OLOAD MODE

ON

 

 

 

 

 

 

00 ...Disabled

 

 

 

 

 

 

 

 

01 ...Enabled for acceleration

 

 

 

 

 

 

 

 

and constant speed

 

 

 

 

 

 

 

 

02 ...Enabled for constant

 

 

 

 

 

 

 

 

speed only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_22

Overload restriction

 

Sets the level for overload

Rated current x 1.25

A

 

setting

 

restriction, between 50% and

 

 

 

 

 

 

 

 

150% of the rated current of

 

 

 

 

 

 

OLOAD LVL 03.75A

 

 

 

 

 

 

the inverter, setting resolution

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is 1% of rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_23

Deceleration rate at

 

Sets the deceleration rate when

1.0

1.0

1.0

 

overload restriction

 

inverter detects overload, range

 

 

 

 

 

 

 

 

is 0.1 to 30.0, resolution is 0.1.

 

 

 

 

 

 

OLOAD CONST 01.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 