| L100 Inverter |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Option | Terminal | Function Name | Input |
|
| Description |
|
|
|
|
|
|
| ||||||
| Code | Symbol | State |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Valid for inputs: | C_01, C_02, C_03, C_04, | Example (some CF inputs require input | |||||||||||||||||
| C_05 |
| ||||||||||||||||||
|
|
|
| configuration; some are default inputs— | ||||||||||||||||
| Required settings: | F_01, A_01 = 02, |
| see page |
|
|
|
|
|
|
| |||||||||
|
|
|
| (MSB) | (LSB) | |||||||||||||||
|
|
| A_20 to A_35 |
|
|
| ||||||||||||||
|
|
|
|
|
| CF4CF3CF2CF1 | ||||||||||||||
|
|
|
|
|
|
| ||||||||||||||
| Notes: |
|
|
| ||||||||||||||||
| • When programming the |
| L | 5 | 4 | 3 | 2 |
| 1 | P24 |
| |||||||||
| sure to press the Store key each time and then set |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| the next |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| key is not pressed, no data will be set. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•When a
is to be set, it is necessary to program the maximum |
|
frequency A_04 high enough to allow that speed. | See I/O specs on page |
|
While using the
There are two ways to program the speeds into the registers A_20 to A_35:
1.Standard keypad programming:
a.Select each parameter A_20 to A_35.
b.Press the FUNC. key to view the parameter value.
c.Use the 1 and 2 keys to edit the value.
d.Use the STR key to save the data to memory.
2.Programming using the CF switches. Set the speed by following these steps:
a.Turn the Run command OFF (Stop Mode).
b.Turn each switch ON and set it to
c. Set the desired output frequency by pressing the 1 and 2 keys.
d.Press the STR key once to store the set frequency. When this occurs, F_01 indicates the output frequency of
e.Press the FUNC. key once to confirm that the indication is the same as the set frequency.
f.Repeat operations in 2. a) to 2. e) to set the frequency of other
Operations Monitoring and